Technical
Data
Approvals and
Maximum Working Pressure
UL & C-UL Listed and NYC Approved:
300 psi (20,7 bar).
FM Approved: 175 psi (12,1 bar).
(Refer to Table A for complete approval
information including corrosion resis-
tant status, as well as the Design Cri-
teria section for applicable system de-
sign criteria.)
Discharge Coefficient
K = 5.6 GPM/psi
1/2
(80,6 LPM/bar
1/2
)
Temperature Ratings
Refer to Table A
Finishes
Sprinkler: Refer to Table A
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated
Physical Characteristics
Frame . . . . . . . . . . . . . Bronze
Button . . . . . . . . . Brass/Copper
Sealing Assembly . . . . . . . . . .
. . . . . Beryllium Nickel w/Teflon†
Bulb . . . . . . . . . . . . . . . Glass
Compression Screw . . . . . Bronze
Deflector . . . . . . . . . . . Copper
Operation
The glass Bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow
Design
Criteria
The S eries TY300-B
Upright
(TY3104), Pendent (TY3204), and
Horizontal Sidewall (TY3304) Sprin-
klers are intended for fire protection
systems designed in accordance with
the standard coverage installation
rules recognized by the applicable
Listing or Approval agency (e.g., UL
Listing is based on the requirements of
NFPA 13, and FM Approval is based
on the requirements of FM’s Loss Pre-
vention Data Sheets).
Only the Style 10 Recessed Escutch-
eon is to be used for recessed instal-
lations.
Installation
The Series TY300-B Sprinklers must
be installed in accordance with the fol-
lowing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F/57°C to 3/32
inch (2,4 mm) for the 360°F/182°C
temperature ratings.
A leak tight 1/2 inch NPT sprinkler joint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with
1/2 NPT connections. Higher levels of
torque may distort the sprinkler inlet
and cause leakage or impairment of
the sprinkler.
Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The
Series TY300-B Pendent and
Upright Sprinklers
must be installed
in accordance with the following in-
structions.
Step 1.
Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2.
With pipe thread sealant ap-
Page 2 of 6
TFP640
TYPE
TEMP.
BULB
LIQUID
NATURAL
BRASS
CHROME
PLATED
WHITE***
POLYESTER
155°F/68°C
175°F/79°C
200°F/93°C
SPRINKLER FINISH (See Note 4)
RECESSED
PENDENT
(TY3204)*
Figure 3
135°F/57°C
Orange
Red
Yellow
Green
1, 2, 3
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL) and for use in Canada (C-UL) for 300 psi.
2. Approved by Factory Mutual Research Corporation (FM) for 175 psi.
3. Approved by the City of New York under MEA 354-01-E for 300 psi.
4. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers
are UL and C-UL Listed as Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) 3/4" Total Adjustment Recessed Escutcheon.
*** Frame and deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS
K
5.6
1/2"
NPT
PENDENT
(TY3204)
and
UPRIGHT
(TY3104)
135°F/57°C
Orange
155°F/68°C
Red
175°F/79°C
Yellow
200°F/93°C
Green
286°F/141°C
Blue
1, 2, 3
RECESSED
HSW
(TY3304)*
Figure 4
135°F/57°C
Orange
155°F/68°C
Red
175°F/79°C
Yellow
200°F/93°C
5.6
1/2"
NPT
HSW
(TY3304)
135°F/57°C
155°F/68°C
175°F/79°C
200°F/93°C
286°F/141°C
Blue
Green
Yellow
Red
Orange
1, 2, 3
Green
1, 2, 3
360°F/182°C
Mauve
360°F/182°C
Mauve
1, 3
OBSOLETE