FIGURE 4, SPACING RULES UNDER PITCHED CEILINGS AND/OR OVERHANGS

S/2 =

ONE-HALF THE LENGTH OF THE COVERAGE AREA BEING HYDRAULICALLY CALCULATED (REF. TABLE A).

S

=

THE LENGTH OF THE COVERAGE AREA BEING HYDRAULICALLY CALCULATED (REF. TABLE A).

NOTE:

Figures 4-1 through 4-9 only apply when:

(a)

the ceiling ridge is horizontal;

(b)

the compartment openings to adjoining spaces have minimum lintel depths of 8 inches below the lowest sprinkler;

(c)

any adjacent sprinklers in the direction of the ceiling ridge are to be in a row which runs parallel to the ridge,
and the sprinklers are to be spaced a minimum of 8 feet apart;

(d)

the sprinklers are installed with their deflector arms perpendicular to the ceiling ridge; and,

(e)

the sprinklers shown in Figures 4-1 through 4-8 are located in a plane which is perpendicular to the ceiling ridge,
and the ceiling angles are within the specified range.

Figure 4-9 (Elevation View)

Figure 4-7 (Elevation View)

Figure 4-5 (Elevation View)

Figure 4-3 (Elevation View)

Figure 4-1 (Elevation View)

Figure 4-10 (Elevation View)

Figure 4-8 (Elevation View)

Figure 4-6 (Elevation View)

Figure 4-4 (Elevation View)

Figure 4-2 (Elevation View)

STAR SPRINKLER

1-3.1.11

Page 5

OBSOLETE

Содержание Star Stealth S240

Страница 1: ...tion required by building codes WARNINGS The Stealth Residential Concealed Pendent Sprin klers described herein must be installed and main tained in compliance with this document as well as with the a...

Страница 2: ...minimum required discharge from the most hydraulically demand ing single sprinkler and the NFPA 13D 13R multiple sprin kler flow rate is the minimum required discharge from each of the total number o...

Страница 3: ...the Protective Cap 3 With pipe thread sealant applied to the pipe threads and using the W Type 13 Wrench positioned as shown in Figure 2 install and tighten the Sprinkler Mounting Cup Assembly into th...

Страница 4: ...and larvae by gently brushing with a feather duster or gently vacuuming with a soft bristle i e dusting brush attachment Exercise suitable safety precautions in the use and storage of highly flammabl...

Страница 5: ...re to be in a row which runs parallel to the ridge and the sprinklers are to be spaced a minimum of 8 feet apart d the sprinklers are installed with their deflector arms perpendicular to the ceiling r...

Страница 6: ...urisdiction The installing contrac tor or sprinkler manufacturer should be contacted relative to any questions It is recommended that automatic sprinkler systems be in spected tested and maintained by...

Страница 7: ...s or parts of products Tyco Fire Products shall not be responsible for sprinkler sys tem design errors or inaccurate or incomplete information supplied by Buyer or Buyer s representatives IN NO EVENT...

Страница 8: ...REQUIRED SLANT DISTANCE BETWEEN A RIDGE AND A SPRINKLER WITHOUT UNDULY OBSTRUCTING THE WATER DISTRIBUTION NOTES 1 UP TO A MAXIMUM OF ONE HALF THE LENGTH OF THE COVERAGE AREA BEING HYDRAULICALLY CALCUL...

Отзывы: