INSTALLATION

The 5.6 and 8.0 K-Factor, Model I-LD-2 Sprinklers must
be installed in accordance with the following instructions:

NOTES

A leak tight 1/2 inch NPT sprinkler joint should be ob-
tained with a torque of 7 to 14 ft.lbs. (9,5 to 14,0 Nm). A
maximum of 21 ft.lbs. (28,5 Nm) of torque is to be used to
install sprinklers with 1/2 inch NPT connections. Higher
levels of torque may distort the sprinkler inlet with conse-
quent leakage or impairment of the sprinkler.

A leak tight 3/4 inch NPT sprinkler joint should be ob-
tained with a torque of 10 to 20 ft.lbs. (13,4 to 26,8 Nm).
A maximum of 30 ft.lbs. (40,2 Nm) of torque is to be used
to install sprinklers with 3/4 inch NPT connections. Higher
levels of torque may distort the sprinkler inlet with conse-
quent leakage or impairment of the sprinkler.

The O-ring seal for pendent sprinklers must be installed
to prevent possible dripping of spray onto the fusible link,
due to clearance between the shield mounting hole and
the threaded end of the sprinkler.

— Upright Sprinklers—

The Model I-LD-2 Intermediate Level Upright Sprinklers
must be installed in accordance with the following instruc-
tions.

1. With pipe thread sealant applied, hand tighten the sprinkler

into the sprinkler fitting.

2. Tighten the sprinkler into the sprinkler fitting using only the

W-Type 9 Sprinkler Wrench (Ref. Figure 3). The wrench
is to be applied to the sprinkler wrenching area shown in
Figure 1 or 2, as applicable.

— Pendent Sprinklers—

The Model I-LD-2 Intermediate Level Pendent Sprinklers
must be installed in accordance with the following instruc-
tions.

1. Roll one of the two required O-Rings over the sprinkler

threads until it seats against the sprinkler wrenching area
flange as shown in Figure 1 or 2, as applicable.

2. Install the Shield over the sprinkler threads, and then roll

the second O-Ring over the sprinkler threads until it is
seated firmly against the Shield.

3. With pipe thread sealant applied, hand tighten the sprinkler

into the sprinkler fitting.

4. Tighten the sprinkler into the sprinkler fitting using only the

W-Type 9 Sprinkler Wrench (Ref. Figure 3). The wrench
is to be applied to the sprinkler wrenching area shown in
Figure 1 or 2, as applicable.

When installed correctly, the O-Rings will be slightly
compressed and the Shield will be held firmly in place.

WRENCH

RECESS

#1849

FIGURE 3

W-TYPE 9 SPRINKLER WRENCH

STAR SPRINKLER

1-4.2.20

Page 3

SPRINKLER FINISH

Temperature

Rating

Frame

Color Code

Natural

Brass

Natural

Brass

135°F/57°C

165°F/74°C

Unpainted

Unpainted

K = 5.6 Upright (S1809)
K = 8.0 Upright (S1822)

Notes:

1. Listed by Underwriters Laboratories, Inc.
2. Listed by Underwriters’ Laboratories of Canada.
3. Approved by Factory Mutual Research Corporation as Rack Storage.
4. Approved by the City of New York under BSA 274-74-SA

TABLE A

LABORATORY LISTINGS AND APPROVALS

1, 2, 4

1, 2, 3, 4

K = 5.6 Pendent (S1801)
K = 8.0 Pendent (S1811)

1, 2, 4

1, 2, 3, 4

212°F/100°C

White

280°F/138°C

Blue

360°F/182°C

Red

1, 2, 4

1, 2, 4

OBSOLETE

Содержание Star I-LD-2

Страница 1: ...y two stainless steel balls holds a fusible alloy When the rated temperature is reached the alloy melts the balls are forced toward each other releas ing the tension mechanism which then allows the sprin kler to activate and flow water TECHNICAL DATA Approvals UL and ULC Listed FM and NYC Approved Refer to Table A The approvals apply only to the service conditions indicated in the Design Criteria ...

Страница 2: ...EDIATE LEVEL SPRINKLERS NPT 1 2 2 5 8 66 7 mm MAKE IN NOMINAL 11 1 mm 7 16 68 3 mm 2 11 16 PENDENT UPRIGHT WRENCHING AREA 3 76 2 mm DIA SHIELD O RINGS FIELD ASSEMBLED SEE INSTALLATION SECTION FACTORY ASSEMBLED WRENCHING FLANGES MAKE IN NOMINAL 11 1 mm 7 16 1 2 NPT FIGURE 2 8 0 K FACTOR MODEL I LD 2 UPRIGHT AND PENDENT INTERMEDIATE LEVEL SPRINKLERS NPT 3 4 2 11 16 68 3 mm PENDENT UPRIGHT WRENCHING ...

Страница 3: ...inkler wrenching area shown in Figure 1 or 2 as applicable Pendent Sprinklers The Model I LD 2 Intermediate Level Pendent Sprinklers must be installed in accordance with the following instruc tions 1 Roll one of the two required O Rings over the sprinkler threads until it seats against the sprinkler wrenching area flange as shown in Figure 1 or 2 as applicable 2 Install the Shield over the sprinkl...

Страница 4: ...ed by companies not affiliated by ownership with Tyco Fire Prod ucts or for products and components which have been subject to misuse improper installation corrosion or which have not been installed maintained modified or re paired in accordance with applicable Standards of the Na tional Fire Protection Association and or the standards of any other Authorities Having Jurisdiction Materials found b...

Отзывы: