DESIGN CRITERIA

The 5.6  K-Factor, Model F960/Q-48
QR-EC Dry Horizontal Sidewall Sprin-
klers must only be installed in accord-
ance with the criteria given in Table A.

The F960/Q-48 Dry Horizontal Side-
wall Sprinklers are to be installed in the
1 inch NPT outlet of a malleable iron
threaded tee fitting per ANSI B16.3 or
cast iron threaded tee fitting per ANSI
B16.4 with the end sprinkler fitting on
a branch line to be plugged as shown
in Figure A.

NOTES

Do not install the F960 into any other

type fitting without first consulting

the Technical Data Department. Fail-

ure to use the appropriate fitting may

result in binding of the inlet Plug or

insufficient engagement of the inlet

pipe threads with consequent leakage.

Branch, cross, and feedmain  piping
that is connected to dry horizontal
sidewall sprinklers and subject to
freezing temperatures must be pitched
for drainage in accordance with  the
minimum requirements of the National
Fire Protection Association for dry pipe
sprinkler systems.

The outer piece of the Escutcheon
Plate cannot be used to hold the
F960/Q-48 Sprinkler in position. Pipe
support must be provided in accord-
ance with the minimum requirements
of the National Fire Protection Asso-
ciation with respect to armovers and
wall mounted sidewall sprinklers.

When dry horizontal sidewall sprin-
klers are to be used on wet pipe sprin-
kler systems protecting areas subject
to freezing temperatures (e.g., coolers
or freezers), consideration must  be
given to the appropriate length of the
sprinkler that will prevent freezing of
the water in the connecting pipes, due
to conduction. The following are the
minimum recommended lengths be-
tween the face of the F960/Q-48 sprin-
kler fitting and the outside surface of
the protected area, when the tempera-
ture surrounding the wet pipe sprinkler
system is maintained at a minimum
temperature of 40°F:

6 inches when the temperature
within the protected area is 0°F;

12 inches when the temperature
within the protected area is -20°F;

18 inches when the temperature
within the protected area is -40°F;
and,

24 inches when the temperature
within the protected area is -60°F.

For protected area temperatures be-
tween those given above, the minimum
recommended length from the face of
the fitting to the outside of the pro-
tected area may be determined by in-

terpolating between the individual val-
ues.

NOTE

When the F960/Q-48 Sprinklers

penetrate a wall into an area subject

to freezing, the clearance space

around the Sprinkler Casing must be

completely sealed, in order to prevent

the leakage of moist air into the freez-

ing area which might result in the

formation of condensate around the

Frame, Deflector, Bulb Seat, or Bulb.

Failure to prevent the formation of

condensate could result in the build-

up of ice around the releasing compo-

nents and, consequently, either an in-

advertant operation of the sprinkler

or, impaired operation due to reduced

thermal sensitivity.

INSTALLATION

NOTES

The Model F960/Q-48 QR-EC Dry

Horizontal Sidewall Sprinkler must

only be installed in fittings that meet

the requirements of the Warning and

Design Criteria sections.
Refer to the Design Criteria section for

other important requirements regard-

ing piping design and sealing of the

space around the Sprinkler Casing.
Do not install any bulb type sprinkler

if the bulb is cracked or there is a loss

of liquid from the bulb. With the

sprinkler held horizontal, a small air

bubble should be present. The diame-

ter of the air bubble is approximately

1/16 inch for the 135°F/57°C and

155°F/68°C temperature ratings.

The sprinkler fitting should be located
so that the face-of-fitting to mounting
surface distance is within plus or mi-
nus 1/4 inch of the sprinkler order
length. The remaining escutcheon
plate adjustment can then be used to
compensate for the possible manufac-
turing variations in the take-out of the
fittings, as well as in the make-in of the
sprinklers (as per mitted by ANSI
B1.20.1).

The F960/Q-48 must be installed with
a deflector to ceiling distance of 4 to 12
inches. To meet this requirement, the
centerline of the sprinkler waterway
(Ref. Fig, A) must be between 4-7/16
and 12-7/16 inches below the ceiling.

The Model F960/Q-48 must be in-
stalled with the centerline of the water-
way horizontal and  perpendicular  to
the back wall surface. The word “TOP”
on the  deflector  must face upwards
toward the ceiling.

-3-

FIGURE D

ESCUTCHEON OUTER PIECE

INSTALLATION PROCEDURE

FIGURE C

LEVELING OF

SPRINKLER FITTING

AND DEFLECTOR

FIGURE B

W-TYPE 7 SPRINKLER WRENCH

OBSOLETE