ing and to reduce the accuracy to
which the sprinkler fitting must be in-
stalled. The 3 inch outside diameter of
the outer piece of the Escutcheon
Plate combined with the 1-3/4 inch di-
ameter clearance hole size also con-
tributes to the ease of installation by
covering offset clearance holes.

The Escutcheon Plate is a separable
two-piece design which allows installa-
tion of the sprinklers and pressure
testing of the fire protection system,
prior to wall construction and/or appli-
cation of a finish coat to the wall. It also
permits refinishing of a wall surface
without having to first shut down the
fire protection system and remove the
sprinklers.

APPROVALS AND STANDARDS

The 5.6  K-Factor, Model F960/Q-48
(SIN G6035) QR-EC Dry Horizontal
Sidewall Sprinklers are listed by Un-
derwriters Laboratories Inc. and Un-
derwriters’ Laboratories of Canada.
They are also accepted by the City of
New York under MEA 39-92-E.

The laboratory listings only apply to
the temperature ratings, order lengths,
sprinkler finishes, and escutcheon

plate finishes stated in Figure A, and
only apply to the service conditions
indicated  in  the Technical Data and
Design Criteria sections.

WARNING

The Model F960/Q-48 QR-EC Dry

Horizontal Sidewall Sprinklers de-

scribed herein must be installed and

maintained in compliance with this

document, as well as applicable

standards of the National Fire Protec-

tion Association, in addition to the

standards of any other authorities

having jurisdiction. Failure to do so

may impair the integrity of these de-

vices.
The owner is responsible for main-

taining their fire protection system

and devices in proper operating con-

dition. The installing contractor or

manufacturer should be contacted

relative to any questions.
The Model F960/Q-48 QR-EC Dry

Horizontal Sidewall Sprinklers must

only be installed in fittings that meet

the requirements of the Design Crite-

ria section.

TECHNICAL DATA

The 5.6  K-Factor, Model F960/Q-48
QR-EC Dry Horizontal Sidewall Sprin-
klers are rated for use at a maximum
service pressure of 175 psi. The avail-
able temperature ratings, order
lengths, sprinkler finishes, and es-
cutcheon plate finishes are given in
Figure A.

The F960/Q-48 must be installed with
a deflector to ceiling distance of 4 to 12
inches. To meet this requirement, the
centerline of the sprinkler waterway
(Ref. Fig, A) must be between 4-7/16
and 12-7/16 inches below the ceiling.

The nominal flow “Q” in GPM (LPM) is
determined by the formula:

where the nominal sprinkler discharge
coefficient “K” equals 5.6 (80,6); and
“p” equals the residual pressure in psi
(bar).

The Plug and Inlet are brass per ASTM
B16 (C36000), and the O-Ring Seal is
silicone rubber. The Casing is galva-
nized carbon steel per ASTM A135
Grade A. The Frame is bronze  per
ASTM B62 (C83600), the Deflector is
brass per ASTM B36 (C22000), the
Compression Screw is bronze per
ASTM B140  (C31400),  and the  two
pieces of the Escutcheon Plate are
0.020 inch thick carbon steel per SAE
1008/1010. The Water Tube is brass
per ASTM B135 (C33000). The Bulb
Seat, Spring, and Yoke are all Type 302
stainless steel. The Guide Tube sub-
assembly is constructed of Type 302
stainless steel and brass per ASTM
B16 (C36000).

Q

K p

=

MIN.

MIN.

W x L

TEMP

FLOW

(b)

PRESSURE

(b)

A

B

APPLICATION

FT x FT

°F

GPM

PSI

INCHES

FEET

QR-EC

(a)

16 x 16

135 & 155

26

21.6

4 to 12

(c)

8

QR-EC

(a)

16 x 18

135 & 155

29

26.8

4 to 12

(c)

8

QR-EC

(a)

16 x 20

135 & 155

32

32.7

4 to 12

(c)

8

QR-EC

(a)

18 x 16

135 & 155

29

26.8

4 to 12

(c)

9

NOTES:

(a) Light Hazard Occupancy automatic sprinkler system applications per NFPA 13.

(b) Requirement is based on minimum flow in GPM from each sprinkler. The indicated residual

pressures are based on the nominal K-Factor.

(c) To meet this requirement, the centerline of the waterway (Ref. Fig. A) must be installed

between 4-7/16 and 12-7/16 inches below the ceiling.

(d) Installation is only permitted for unobstructed, smooth level ceiling construction as defined

in NFPA 13.

(e) Follow the requirements of NFPA 13 for spacing between the sprinklers and ceiling mounted

obstructions.

TABLE A

INSTALLATION CRITERIA FOR 1/2 INCH ORIFICE

MODEL F960/Q-48 QR-EC DRY HORIZONTAL SIDEWALL SPRINKLERS

-2-