restored to normal standby condition. If the system is in test mode, pressing the reset button will take 
the CP-3500D out of test mode. If any Alarm, Supervisory or Trouble that exists after reset will cause 
the system to once again annunciate that condition. 

 

Panel Test 
Pressing this button while the CP-3500D is in normal standby will activate the Test LED. Refer to the 
system testing section for additional information. Pressing reset will return the system to normal 
standby. 

 

Horns On 
When pressed, this button will activate any NAC circuits and/or Model 301 sounders, turn the piezo 
on steady and the words “Alarm Circuits Activated will appear on the LCD screen. Pressing this 
button will also send a record to the button press log. 

The Horns On button must be programmed 

to perform these functions. Refer to programming section for options.

  

 

Enter 
This button is used for system programming. Refer to programming section. 

 

Back 
This button is used for system programming. Refer to programming section. 
 
Up, Down, Left, Right  
These buttons are used for system programming and LCD display navigation.  
 
4 Soft arrow keys  
These buttons provide access to the menus used for configuration, programming, memory logs and 
system info. They also provide other functions where necessary.  The user may be prompted to enter 
the pass code when accessing programming functions with any of these buttons. The current button 
function will appear on the LCD screen just above the buttons.  

 

 

Figure 7 

Содержание CWSI CP-3500D

Страница 1: ...ghts reserved All specifications and other information shown were current as of document revision date and are subject to change without notice CP 3500D WIRELESS FIRE ALARM CONTROL PANEL OPERATING and...

Страница 2: ...e suitability of their products for a specific installation site or for a specific application Local testing for suitability of both the proposed site and application is required Unless prohibited by...

Страница 3: ...Receiving and Unpacking the Equipment 13 3 4 Installing the CP 3500D 13 3 4 1 Enrolling Devices Annunciators and Repeaters 17 3 4 2 Installing the Annunciators Repeaters and Devices 19 3 4 3 The Back...

Страница 4: ...and Deactivation 44 4 8 4 Remote Reset Feature 45 4 9 Unknown and Ignored Units 45 4 9 1 Displaying the Unknown Unit Screen 45 4 9 2 Removing a Device from the Unknown List 46 4 9 3 Displaying the Ig...

Страница 5: ...mming Information 67 6 2 9 Accessing the System Info Screen 67 6 2 10 Accessing the Programming info Screen 68 SECTION 7 DIGITAL ALARM COMMUNICATORS 70 7 1 Silent Knight Model 5104B 70 7 1 1 Installat...

Страница 6: ...70 National Electrical Code The model CP 3500D is the first in a series of wireless fire annunciation and control panels manufactured by CWSI This system was designed and tested to comply with NFPA 7...

Страница 7: ...is also compatible with UL Listed Communicators making the CWSI CP 3500D a complete installation solution The system is designed with monitoring and emergency personnel in mind The LCD display provid...

Страница 8: ...detector control 24 or 60 hour battery standby time 24 Volt Class A B NAC circuits 4 N O alarm dry contact outputs 2 form C programmable dry contact alarm outputs 1 form C trouble output Auxiliary mun...

Страница 9: ...Limited 1 Class A Style Z or 2 Class B Style Y Field selectable Class A ratings 24 Volts DC 1 Amp Class B ratings 24 Volts DC 1 Amp each Regulated NAC Circuits Programmable Non power Limited 1 Class A...

Страница 10: ...nation Smoke Heat Detector Pull Station Model 310 Manual Pull Station Fire Transmitter Models 345 TS N O EOL Supervised Transmitter CO Detector Model 350 Carbon Monoxide Detector with Integral Sounder...

Страница 11: ...software In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems UL 864 certain programming features or options must be limite...

Страница 12: ...CWSI IM C3K5D Rev H 2017 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice 12 Figur...

Страница 13: ...appliance facp in an installation is 30 This limitation insures that the UL and NFPA 10 second alarm requirement is met 3 Maximum number of devices per repeater or direct to the CP 3500D is 100 A rep...

Страница 14: ...now be installed into the provided knockout locations Power limited and non power limited wiring must be in separate conduit and kept a minimum of 25 apart in the enclosure Refer to figure 4 for sugge...

Страница 15: ...date and are subject to change without notice 15 6 Connect the supplied cable between the repeater and the antenna The cable should be within the same room and not routed near electrically noisy sour...

Страница 16: ...unciators and repeaters that are in the CP 3500D memory The CP 3500D will also verify and or update any relay programming for the repeaters according to the current CP 3500D programming memory An esti...

Страница 17: ...se code into the device and stores the serial number into the CP 3500D memory The main system normal screen must be showing before the CP 3500D can be placed into enrollment mode If any alarms or trou...

Страница 18: ...dy has a base code programmed in it Clear the base code from the unit Refer to the individual device manual for instructions on how to clear the base code The screen below will be present on the LCD w...

Страница 19: ...d from the sounder in the device being tested Once the device is mounted confirm acceptable signal strength once more to insure proper operation After the device has been installed and signal verified...

Страница 20: ...should be on the left and the red wire on the right when it is connected properly We recommend replacing the batteries in accordance with NFPA 72 guidelines or every three years After replacing the b...

Страница 21: ...CWSI IM C3K5D Rev H 2017 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice 21 Figur...

Страница 22: ...ude 4 Softkey Up Down Left Right Enter and Back buttons See figure 3 below for the location of these buttons The Up Down Left Right buttons are used for menu navigation and character number selection...

Страница 23: ...e CP 3500D will revert back to the main screen and any unsaved changes will be lost If an Alarm or Supervisory signal is received while in any menu the CP 3500D will abort the menu programming functio...

Страница 24: ...n date and are subject to change without notice 24 Device Enrollment Ignored Units Unknown Units A V Device Tandem Controls CP 3500D Relay Setup Device Edit Program CP 3500D Relay Setup Supervisory Se...

Страница 25: ...is showing and you will have access to the menus If ENTER is pressed with any of the wrong characters showing or 4 numbers are not entered the field will clear and the entire password will have to be...

Страница 26: ...s this soft key to save the changes or CANCEL to abort all changes to the page If you press the BACK key without saving a screen will appear asking if you want to save Press the appropriate soft key a...

Страница 27: ...the ENTER key and the screen below will be shown The three menu items shown are important to verify and change if necessary before continuing to the system main screen and performing any other progra...

Страница 28: ...the AM PM field and set it When you have time correctly set press the ENTER key to stop edit mode Use the same procedure to set the date and the Auto Update DST setting When the DST is off the clock...

Страница 29: ...reception range of any device repeater or CP 3500D in the same or a different installation Warning You must verify that each CP 3500D in reception range of another has different base codes before enr...

Страница 30: ...ress ENTER Use the UP DOWN buttons to choose On or Off then press enter When you are done making the desired changes press the Save soft key to save the change and display the Initial Configuration Me...

Страница 31: ...ksum bad trouble on all installed annunciators To correct this trouble update the programming in all installed annunciators as described in the WRA 3 manual Any devices or repeaters that have not been...

Страница 32: ...e appropriate selection when prompted 4 4 2 Deleting a Device annunciator or repeater To delete a device annunciator or repeater from the system 1 Locate the Device s Annunciator s and or Repeater s y...

Страница 33: ...to be in alarm in order for the zone to become active The third group 890 895 is reserved for future use The fourth group 896 899 is the global zones group for tandem devices Only 899 is in use at thi...

Страница 34: ...Assignment The CP 3500D has 4 levels of alarm which can be assigned to initiating devices These alarm levels are referred to as A B C and D A is the highest priority and D is the lowest Level C can b...

Страница 35: ...evice type as CP 3500D and the description field will be blank The description is limited to 16 characters and can contain letters numbers and symbols To enter or change a description access the devic...

Страница 36: ...se the next device to edit or continue to press BACK until the main CP 3500D screen is displayed 4 4 7 Point ID A Point ID number is automatically assigned to each repeater annunciator and device that...

Страница 37: ...page down soft keys to locate the desired repeater then press ENTER The following screen will be shown for the selected repeater The screen will show the default selections unless the selected relay...

Страница 38: ...to select Horns On then press ENTER to exit edit mode Activated relays will always be deactivated if the RESET key is pressed An additional keypad button can also be selected to deactivate the relay...

Страница 39: ...which reads Last Update Pending Unable to Edit If this occurs back out of the relay edit screen and wait a few minutes then try again You will be allowed to edit the information once the CP 3500D is...

Страница 40: ...programmed to deactivate an output The default to turn off these outputs is Signal Silence The available selections are Signal Silence and Reset Selecting Reset will keep the output activated until th...

Страница 41: ...ication The supervisory signals can also be programmed to auto restore This option if desired should be chosen during system setup if possible Turning supervisory auto restore or alarm C supervisory o...

Страница 42: ...del 302 is a self contained smoke detector with no sounder intended for installation in common areas The model 302 will transmit an alarm when it senses smoke The model 320 is a self contained heat de...

Страница 43: ...99 is activated all of the model 301 smoke alarms will turn on their sounders Zone 899 is not required to be entered as any of the three zones in a model 301 for this feature to work The 301 detectors...

Страница 44: ...Device On is None This means the tandem detector sounders in the installation will only be activated by zones The Horns On button can be selected to activate all tandem sounders To program the Horns...

Страница 45: ...owing reasons 1 The device was deleted from the CP 3500D without removing the battery and allowing it to show a test failure trouble first As soon as the device tries to check in it will be reported a...

Страница 46: ...f you cannot identify it as being part of your installation If you are receiving unknown units that you cannot identify which may be from another installation the correct solution is to change the bas...

Страница 47: ...an unknown device trouble Devices can remain on the ignored list indefinitely Warning The CP 3500D will not respond to alarms supervisory or troubles received from devices on the ignored list To remo...

Страница 48: ...CWSI IM C3K5D Rev H 2017 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice 48 Figur...

Страница 49: ...quipment to properly monitor any wiring fault Refer to the communicator section of this manual for approved communicator and proper connection The contacts are rated at 24Volts D C 1 Amp resistive Acc...

Страница 50: ...This is a programmable output for connection to a city municipal box using series connection only Shunt connection is not supported This is a non power limited connection Power limited and non power...

Страница 51: ...s All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice 51 Note The trouble form C relay output will not...

Страница 52: ...ent sensing technology and if the rated current draw is exceeded a NAC overload trouble signal will be displayed and the NAC circuit output will deactivate It will attempt to reactivate only if anothe...

Страница 53: ...SW HORN STROBE 4 WHEELOCK DSM 12 24 R SYNC MODULE 1 SYSTEM SENSOR P2R P2W HORN STROBE 4 SYSTEM SENSOR MDL3R or MDL3W SYNC MODULE 1 SYSTEM SENSOR R 20E RELAY 4 CWSI 520 R W L F SOUNDER CWSI MH R W MINI...

Страница 54: ...power cycling the CP 3500D 5 2 5 USB Jack J35 on receiver This connector is for factory use only Refer to figure 6 for location 5 2 6 Ethernet Connection The Ethernet connector is located on the bott...

Страница 55: ...stment is provided to accommodate installation locations which make the factory setting difficult to view the displayed information It is located under the keypad on the main CP 3500D board adjacent t...

Страница 56: ...ming All button presses involving operation of the CP 3500D and every time the pass code is entered will be stored in the button press log for later retrieval if needed The Back Enter Up Down Left Rig...

Страница 57: ...this button is pressed while an alarm is present Pressing this button will also send a record to the button press log The Signal Silence button must be programmed to perform any of these functions Fo...

Страница 58: ...circuits and or Model 301 sounders turn the piezo on steady and the words Alarm Circuits Activated will appear on the LCD screen Pressing this button will also send a record to the button press log T...

Страница 59: ...ends a different type of Trouble If the CP 3500D is not reset to normal within 4 hours of acknowledging a Trouble the sounder will reactivate with the trouble pattern to indicate the acknowledged devi...

Страница 60: ...embrane buttons will function as described in section 6 1 3 If unacknowledged lower priority signals are present they can be displayed as each higher priority signal is acknowledged The LCD display sh...

Страница 61: ...down soft keys will appear when number of signals spans more than one LCD page Use these keys to view supervisory alarms on other pages 6 2 5 Trouble Signals A trouble signal indicates a problem with...

Страница 62: ...Can occur in an AR 5 repeater or CP 3500D control panel Caused by a NAC or Auxiliary output wiring short to earth ground of 1000 ohms or less Check the wiring for shorts to earth ground This trouble...

Страница 63: ...he batteries 12 Low Battery2 Can occur in a 520 or MH audible notification device Caused by horn driver battery voltage being too low or faulty batteries Replace the batteries 13 Maintenance Req Can o...

Страница 64: ...into test mode while the System Normal screen is showing To enter the test mode press the PANEL TEST button All of the leds will flash three times then the CP 3500D will display the test mode screen...

Страница 65: ...de This log cannot be erased Limit is 1000 events 2 Trouble Log Records all Trouble events while the CP 3500D is not in test mode This log cannot be erased Limit is 1000 events 3 All Event Log Records...

Страница 66: ...g Pg Down A l l E v e n t L o g R e s e t 1 2 1 0 0 0 A M 0 1 0 2 0 9 S u p e r v i s o r y 0 3 3 a 9 2 1 2 0 2 0 4 A M 0 1 0 2 0 9 T a m p e r S w i t c h B a s e m e n t 2 H o r n s O n 1 2 0 2 0 0...

Страница 67: ...enu will now be shown Highlight System Info and press enter The screen below will be shown System Info Screen The information on the System Info screen is mainly used for technical assistance If you c...

Страница 68: ...o divider Use the PAGE UP PAGE DOWN LAST PAGE and TOP PAGE soft keys to view all of the information The programming is presented in a slightly different format than it is in the actual programming scr...

Страница 69: ...8 U n i t 0 3 d 9 1 3 F l o w S w i t c h Z o n e 1 0 2 5 Z o n e 2 0 0 0 Z o n e 3 0 0 0 P r i o r i t y B D e s c B a s e m e n t P o i n t I D 0 0 1 0 12 33 20PM 08 14 09 Last Pg Pg Down P r o g r...

Страница 70: ...ze recommended in the 5104B manual All of the wiring is power limited Always run power limited and non power limited wiring in separate conduit Maintain at least between power limited and non power li...

Страница 71: ...he 5104B will transmit the notification to the central station Acknowledging the alarm on the CP 3500D will only silence its internal sounder The sounder on the 5104B CANNOT be silenced by pressing th...

Страница 72: ...rt on the SDACT 2 so point ID numbers can be transmitted to the central station for each enrolled repeater and device The communicator has the capability of either 24 or 60 hour battery backup time 7...

Страница 73: ...to report to the central station properly Refer to the SDACT 2 manual for further information Once the wiring and programming of the CP 3500D and SDACT 2 are complete any alarms supervisory or trouble...

Страница 74: ...hed communicating to the central station A restore signal will be sent to the central station upon restoring the CP 3500D to normal standby When a trouble is displayed by the CP 3500D the N C contacts...

Страница 75: ...larm B Reset FH Fire Alarm Restore Alarm C FA Fire Alarm Alarm C Reset FH Fire Alarm Restore Alarm C Supervisory FS Fire Supervisory Alarm C Supervisory Reset FV Fire Supervisory Restore All Troubles...

Страница 76: ...urvey location of the transmitter being used Once the initial beep is heard the magnet can be removed while waiting for the confirmation signal Continue this until the one beep and two beep confirmati...

Страница 77: ...type of transmitter One beep should be heard at the device and the repeater which received the survey signal followed by either a single beep or two beeps at the device only A single beep indicates an...

Страница 78: ...9 Enrollment 8 19 EOL Violation 63 F Features 8 G Ground Fault 62 H Hardware Failure 62 Horns On 58 I Ignored Device 46 Initiating Device 7 8 10 13 19 56 57 59 60 61 62 63 64 Installation 13 Introduc...

Страница 79: ...64 Smoke Detector 7 8 49 63 Smoke Detector Silence 57 Soft Keys 58 Sounder 7 56 57 59 60 61 76 Specifications 9 Strobe Reset 57 Supervisory 7 49 50 59 60 61 Supervisory Ack 56 Survey Button 77 System...

Страница 80: ...ble signals press the TROUBLE ACK button To view multiple pages of Trouble signals press the PAGE UP or PAGE DOWN soft keys To activate evacuation horns press the HORNS ON button To silence evacuation...

Отзывы: