Temperature Rating: 200

°

F/93

°

C

Hydraulic Design Criteria:
The density required is 0.80 gpm/sq. ft. (32.6 mm/min).

Design Area:   For wet systems 2000 sq. ft. (186 m

2

)

and for dry systems use 4500 sq. ft.
(418.5 m

2

)

Spacing:  Maximum spacing is 100 sq. ft. (9.3 m

2

) and

the minimum is 70 sq. ft. (6.5 m

2

).  The

maximum distance between sprinklers is

  12'-0" (3.7 m) - 12'-6"(3.8 m) spacing is

allowed in 25'-0"(7.6 m) bays.  Minimum
spacing is 6'-0" (1.8 m) apart unless
separated by baffles.

Obstructions:  NFPA criteria for standard spray
                         sprinklers.

Type of Storage:  Single, double, multiple-row and

portable rack storage (No Solid
Shelves) and solid piled or
palletizied storage.

Commodity:  Class I-IV, encapsulated or non-

encapsulated.  Group A and B plastics -
cartoned, expanded or unexpanded as
well as exposed, unexpanded.

Maximum Storage Height: 25'-0" (7.6 m)

Clearance:  36" (914 mm) minimum from deflector to
                    top of storage.

Max. Ceiling Height in Area of Storage: 30'-0" (9.1 m)

Construction Type:  All types - deflector distances per
                                   NFPA 13.

System Type:      Wet or dry

Table 2 - ULTRA

 

K17 UL & C-UL Specific Application Guidelines

Table 3 - ULTRA K17 Factory Mutual Specific Application Guidelines

Hydraulic Design Criteria:

   Class I & II commodities:

   Class III, & IV, and cartoned
   and Uncartoned unexpanded
   Group A and B plastics:

Design Area:   Calculate the Hydraulicaly most

demanding 5 Sprinkler Heads on 3
Branch Lines.

Spacing:  Maximum spacing is 100 sq. ft. (9.3 m

2

) and

the minimum is 80 sq. ft. (7.4 m

2

).  The

maximum distance between sprinklers is

   12'-0" (3.7 m).  Minimum spacing is 8'-0"

(2.4 m).

Other Details:

     See Factory Mutual Loss

Prevention Data Sheets 8-9

Type of Storage:  Single, double, multiple-row and

portable rack storage (No Solid
Shelves) and solid piled or
palletizied storage.

Maximum Storage Height:   25'-0"(7.6 m)

Clearance:  36" (914 mm) minimum from deflector to
                    top of storage.

Max. Ceiling Height in Area of Storage:  30'-0" (9.1 m)

Construction Type:  All types - deflector distances per
                                  Factory Mutual Loss Prevention
                                  Data Sheets 2-8N.

System Type:       Wet & Single Interlock Preaction

Temperature Rating:   155

°

F/68

°

C or 200

°

F/93

°

C

15 Sprinklers at
22 psi (1.5 bar)

15 Sprinklers at
10 psi (0.7 bar)

OBSOLETE