background image

Figure 4 - LF Sprinkler Wrench (1025)

Figure 3 - Model LF Extended Pendent

Finished Ceiling

LIne

399

Escutcheon

Face of

Reducing

Coupling

6"

(152,4mm)

 Max.

3-3/4"

(95,3mm)

 Min.

3-1/2" 

(88,9mm)

 Max.

2-1/4"

(57,2mm)

 Min.

1-11/16"

(42,9mm)

399 Escutcheon

Finish

Part#

Brass

1287

Chrome

1286

White

1288

Off-White 1290

TIA 99-1 (Tentative Interim Ammendment) with an effective date
of May 22, 2000 states that the minimum required discharge from
each of the "design sprinklers" for systems designed to NFPA 13
must be calculated based on delivering a minimum design density
of 0.1 gpm/sq. ft. for each of the listed coverage areas shown in
Table 1, Table 2, Table 3, or Table 4.  Consult the authority having
jurisdiction regarding the application of this TIA to the currently
adopted NFPA 13.

Model LF Residential Pendent and Recessed Pendent Sprinklers
must be installed using the obstruction criteria for extended
coverage sprinklers found in the current edition of NFPA 13.

NOTES

Residential Fire Sprinkler Systems should only be designed
and installed by those competent and completely familiar
with automatic sprinkler system design, installation
procedures, and techniques.

The sprinkler must be secured in position by firmly fastening
the sprinkler system piping to the structure. If the sprinkler is

Figure 1 - Model LF Pendent

Figure 2 - Model LF Recessed Pendent

1-3/16" (30,2 mm)

Diameter

2-1/8"

(54,0 mm)

Reducing

upling

11/16"

,9 mm)

Ref.

WRENCH 

FLAT

1-3/16" (30,2 mm)

Diameter

2-1/8"

(54,0 mm)

Face of

Reducing

Coupling

1/2" 

(12,7mm)

Max.

1/8" 

(3,2mm)

Min.

 1-9/16" Max.

 

(39,7mm)

1-3/16" Min.

(30,2mm)

2-7/8"(73,0 mm) Diameter

Finished Ceiling Line

Model BV  Res./QR

Recessed Escutcheon

2"

(50,8 mm)

Minimum Diameter

2-1/4" 

(57,2 mm)

Maximum Diameter

not properly secured in position, reaction forces resulting
from sprinkler operation could alter its orientation and its
water distribution pattern. The sprinkler escutcheon cannot
be used to hold the sprinkler in position.

Several criteria may apply to the installation and usage of
each sprinkler. Consequently, it is recommended that the
sprinkler system designer review and develop a working
understanding of the complete list of criteria prior to initiating
the design of the sprinkler system.

Questions concerning sprinkler installation and usage
criteria, which are not covered by the following instructions,
should be submitted to Central Sprinkler. Include sketches
and technical details as appropriate.

In some instances, the requirements of this document may
concern specifications which are more stringent and which
take precedence over those specified in NFPA 13, NFPA 13D,
NFPA 13R, or by the authority having jurisdiction.

OBSOLETE

Содержание CENTRAL LF

Страница 1: ...They are to be used in wet pipe residential sprinkler systems for one and two family dwellings and mobile homes per NFPA 13D wet pipe residential sprinkler systems for residential occupancies up to an...

Страница 2: ...18 8 psi 5 5 x 5 5m 53 0 lpm 1 50 bar 49 2 lpm 1 30 bar 20 x 20 16 GPM 28 4 psi 16 GPM 28 4 psi 6 1 x 6 1m 60 6 lpm 1 96 bar 60 6 lpm 1 96 bar Minimum Design Flow Coverage Multiple Area Single Sprinkl...

Страница 3: ...kler system piping to the structure If the sprinkler is Figure 1 Model LF Pendent Figure 2 Model LF Recessed Pendent 1 3 16 30 2 mm Diameter 2 1 8 54 0 mm Reducing upling 11 16 9 mm Ref WRENCH FLAT 1...

Страница 4: ...A minimum of 4 verify G dimension minimum of 4 maximum 1 2 of the Listed spacing that the sprinkler was calculated for i e 18 x 18 spacing is maximum of 9 0 from a wall B For angles 0 to 39 minimum B...

Страница 5: ...e minimum distance between sprinklers is measured horizon tally shown as dimension E Staggering the sprinklers will help maintain minimum horizontal distances in difficult situations Dimensions A and...

Страница 6: ...secting a Flat Ceiling First verify that D is Acceptable or Obstructed per Figure 14 If Acceptable Figure 12 applies If Ob structed additional sprinklers will be necessary to protect the flat ceiling...

Страница 7: ...f the Sprinkler has been damaged replace the entire Sprinkler assembly Do not attempt to modify or repair a damaged sprinkler Step 6 Push the outer ring of the Recessed Escutcheon over the Re cessed S...

Страница 8: ...ang anything from the sprinklers Do NOT cleanse the sprinklers with soap and water detergents ammo nia cleaning fluids or other chemi cals Remove dust lint cobwebs cocoons insects and larvae by gently...

Отзывы: