National Fire Protection Associa-
tion, in addition to the standards of
any other authorities having
jurisdiction. Failure to do so may
impair the integrity of these de-
vices.

Because of the above cited stipula-
tions and the varied nature of
residential type architecture, there
will be some compartment designs
which cannot be fully sprinklered in
accordance with the recomendations
of NFPA 13, NFPA 13D, or

NFPA 13R. In the event of this
condition, consult the authorities
having jurisdiction for guidance
and approval.

The owner is responsible for
maintaining their fire protection
system and devices in proper
operating condition. The installing
contractor or sprinkler manufac-
turer should be contacted relative
to any questions.

Sprinkler Identification Number
SIN C1296 - (155

°

F/68

°

C)

SIN C1297 - (175

°

F/68

°

C)

Approvals
UL & C-UL Listed. MEA (323-98-E)
(Refer to the Design Criteria Section)

Maximum Working Pressure
175 psi (12,1 bar)

Pipe Thread Connection
1/2 inch NPT

Discharge Coefficient
K = 3.0 GPM/psi

1/2

 (43,2 LPM/bar

1/2

)

Temperature Ratings
155

°

F/68

°

C or 175

°

F/79

°

C

Finishes
Sprinkler: White Polyester, Chrome
Plated, or Natural Brass

Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated

Tyco Fire Products --- www.centralsprinkler.com
451 North Cannon Avenue, Lansdale, Pennsylvania 19446 --- USA
Customer Service/Sales: Tel: (215) 362-0700 / Fax: (215) 362-5385
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500

Model LF

No. 4-1.0

3.0 K-factor -
Fast Response Residential

Pendent & Recessed Pendent Glass Bulb Automatic Sprinkler

General
Description

The Central Model LF, 3.0 K-factor
Residential Pendent and Recessed
Pendent sprinklers are decorative
glass bulb sprinklers designed for use
in residential occupancies such as
homes, apartments, dormitories, and
hotels.

They are to be used in wet pipe
residential sprinkler systems for one-
and two-family dwellings and mobile
homes per NFPA 13D; wet pipe
residential sprinkler systems for
residential occupancies up to and
including four stories in height per
NFPA 13R; or, wet pipe sprinkler
systems for the residential portions of
any occupancy per NFPA 13.

The Central Model LF Residential
Pendent Sprinklers have a 3.0 K-
factor which provides very low design
flow rates at reduced residual pres-
sures, enabling smaller pipe sizes and
water supply requirements.

The recessed version of the Model LF
Residential Pendent Sprinkler is
obtained by utilizing the Model LF
Residential Pendent Sprinkler in
combination with the Model BV Res./
QR Recessed Escutcheon Assembly.
The recessed version of the Central
Model LF using a Model BV Res./QR
Recessed Escutcheon provides up to
3/8 inch (9,5 mm) of total adjustment
from the flush pendent position.

Operation: The glass bulb contains a
fluid which expands when exposed to
heat. When the rated temperature is
reached, the fluid expands sufficiently
to shatter the glass bulb, which then
allows the sprinkler to activate and
flow water.

WARNING

The LF Residential Pendent Sprin-
klers described herein must be
installed and maintained in compli-
ance with this document, as well as
with the applicable standards of the

Technical
Data

CENTRAL

LF Pendent

7-02

Residential
Pendent and
Recessed
Pendent
Sprinklers

Physical Characteristics
The Model LF Residential Pendent
Sprinkler utilizes a dezincification
resistant (DZR) bronze frame and a
2.5 mm bulb for 175

°

F and a 3 mm

bulb for 155

°

F. The sprinkler frame

orifice is sealed with a  gasketed
spring plate (Belleville Seal) consist-
ing of a beryllium nickel disc spring
that is sealed on both its inside and
outside edges with a Teflon

TM

 gasket.

The compression screw is bronze,
and the deflector is brass.

SPRINKLERS FOR REPLACEMENT USE ONLY IN EXISTING SPRINKLER SYSTEMS

OBSOLETE

Содержание CENTRAL LF

Страница 1: ...They are to be used in wet pipe residential sprinkler systems for one and two family dwellings and mobile homes per NFPA 13D wet pipe residential sprinkler systems for residential occupancies up to an...

Страница 2: ...18 8 psi 5 5 x 5 5m 53 0 lpm 1 50 bar 49 2 lpm 1 30 bar 20 x 20 16 GPM 28 4 psi 16 GPM 28 4 psi 6 1 x 6 1m 60 6 lpm 1 96 bar 60 6 lpm 1 96 bar Minimum Design Flow Coverage Multiple Area Single Sprinkl...

Страница 3: ...kler system piping to the structure If the sprinkler is Figure 1 Model LF Pendent Figure 2 Model LF Recessed Pendent 1 3 16 30 2 mm Diameter 2 1 8 54 0 mm Reducing upling 11 16 9 mm Ref WRENCH FLAT 1...

Страница 4: ...A minimum of 4 verify G dimension minimum of 4 maximum 1 2 of the Listed spacing that the sprinkler was calculated for i e 18 x 18 spacing is maximum of 9 0 from a wall B For angles 0 to 39 minimum B...

Страница 5: ...e minimum distance between sprinklers is measured horizon tally shown as dimension E Staggering the sprinklers will help maintain minimum horizontal distances in difficult situations Dimensions A and...

Страница 6: ...secting a Flat Ceiling First verify that D is Acceptable or Obstructed per Figure 14 If Acceptable Figure 12 applies If Ob structed additional sprinklers will be necessary to protect the flat ceiling...

Страница 7: ...f the Sprinkler has been damaged replace the entire Sprinkler assembly Do not attempt to modify or repair a damaged sprinkler Step 6 Push the outer ring of the Recessed Escutcheon over the Re cessed S...

Страница 8: ...ang anything from the sprinklers Do NOT cleanse the sprinklers with soap and water detergents ammo nia cleaning fluids or other chemi cals Remove dust lint cobwebs cocoons insects and larvae by gently...

Отзывы: