SPRINKLER FINISH
Temperature
Frame Natural Chrome
Polyester
Rating
Color Code
Brass Plated
Coated
165
°
F/74
°
C
Unpainted
212
°
F/100
°
C
White
Table 1 - Laboratory Listings and Approvals
Notes:
1. Listed by Underwriters Laboratories, Inc.
2. Listed by Underwriters' Laboratories of Canada.
3. Approved by Factory Mutual Research Corporation.
4. Approved by the City of New York under BSA 375-75-SA
Design
Criteria
The Model H Recessed Pendent Sprinklers are UL, ULC Listed and MEA Approved for use in accordance with current NFPA
standards. The Recessed Pendent Sprinklers are only listed with the Series A/H Recessed Escutcheon Assemblies.
The Model H Recessed Pendent Sprinklers are FM Approved for use in accordance with the FM Loss Prevention Data
Sheets. The Recessed Pendent Sprinklers are only listed with the Series A/H Recessed Escutcheon Assemblies.
The Model H Recessed Pendent Sprinklers are availabe with a two types of support cups, one that accepts a push-on
escutcheon and one that accepts a threaded escutcheons. The recessed escutcheons are manufactured out of a metal or
plastic material that has been specifficaly tested and listed for use with the Model H Recessed Pendent Sprinklers. The
plastic recessed escutcheon is only listed for use with the push-on support cup assembly.
Do not install the Model H Recessed Pendent Sprinklers in ceilings which have positive pressure in the space above.
The Model H Recessed Pendent
Sprinklers
must be installed in accor-
dance with the following instructions.
NOTES
A leak tight 1/2 inch NPT sprinkler joint
should be obtained with a torque of 7 to
14 ft.lbs. (9,5 to 19,0 Nm). A maximum
of 21 ft.lbs. (28,5 Nm) of torque is to be
used to install 1/2 inch NPT sprinklers.
Higher levels of torque may distort the
sprinkler inlet with consequent leakage
or impairment of the sprinkler.
Do not attempt to make up for insuffi-
cient adjustment in the escutcheon plate
by under- or overtightening the sprin-
kler. Readjust the position of the
sprinkler fitting to suit.
Installation
Step 1. Pendent sprinklers must be
installed only in the pendent position.
The deflector is to be parallel to the
ceiling, roof, or mounting surface, as
applicable.
Step 2. With pipe thread sealant applied
to the pipe threads, hand tighten the
sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the Universal
Wrench (Ref. Figure 4). With reference
to Figure 1 or 2, the Universal Wrench
is to be applied to the sprinkler wrench
flats only.
After the ceiling has been installed or
the finish coat has been applied, slide
on the Model A/H Recessed Escutcheon
over the Model H Recessed Sprinkler
and push-on or thread on the recessed
escutcheon until its flange comes in
contact with the ceiling.
1,2,3,4 1,2,3,4
1
1,2,3,4 1,2,3,4
1
Installation of the Model A/H Reccesed
Escutcheon can be accomplished by
hand or by using the Recessed
Escutcheon Tool (Ref. Figure 5) and a
telescoping pole assembly. Every
Model H Recessed Escutcheon has 4
tabs on the interior opening of the
escutheon. By matching these tabs to
the corresponding groove on the
Recessed Escutcheon Tool and with
the telescoping pole attached, the
recessed escutcheon can be installed
without the aid of a ladder. Care should
be exercised to assure that the Actuator
Rod and Ejector Springs of the sprinkler
are not dammaged during the installa-
tion of the recessed escutcheon.