Fire Protection Association, in addition
to the standards of any other authorities
having jurisdiction. Failure to do so may
impair the integrity of these devices.

The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.

Sprinkler Identification Number
SIN C3711

Approvals
UL & ULC Listed. FM & NYC Approved
(Refer to Table 1. The approvals apply
only to the service conditions indicated
in the Design Criteria Section)

Maximum Working Pressure
175 psi (12,1 bar)
250 psi (17,3 bar) UL & ULC

Pipe Thread Connection
1/2 inch NPT

Discharge Coefficient
K = 5.6 GPM/psi

1/2

 (80,6 LPM/bar

1/2

)

Temperature Ratings
165

°

F/74

°

C or 212

°

F/100

°

C

Finishes
Sprinkler: White Polyester, Chrome
Plated, or Natural Brass
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated

Physical Characteristics
The Model H Recessed Pendent
Sprinklers utilize a dezincification resistant
(DZR) bronze frame and a brass deflector.
The waterway is sealed with copper seal
disk, and the fusible assembly is con-
structed of bronze and stainless steel
components.

Tyco Fire Products --- www.centralsprinkler.com
451 North Cannon Avenue, Lansdale, Pennsylvania 19446 --- USA
Customer Service/Sales: Tel: (215) 362-0700 / Fax: (215) 362-5385
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500

Model H Recessed

No. 1-3.0

5.6 K-factor
Standard Response
Standard Coverage

Recessed Pendent Fusible Solder Type Sprinkler

General
Description

The Central Model H, 5.6 K-factor
Recessed Pendent Sprinklers  are
automatic sprinklers of the fusible solder
type. They are standard response -
standard orifice spray sprinklers
intended for use in fire sprinkler
systems designed in accordance with
the standard installation rules recog-
nized by the applicable Listing or
Approval agency (e.g., UL Listing is
based on NFPA 13 requirements).

The Central Model H Recessed
Pendent Sprinklers incorporate a center
strut mechanism with a special two-
piece recessed escutcheon assembly
permitting 1/2" of field-adjustment.
Unlike most other recessed sprinklers,
the upper escutcheon support piece is
factory installed on the base of the
sprinkler frame, assuring a Listed
installation.  The ceiling escutcheon
plate is easily installed after the
sprinkler is in place either by the
standard “push-on” escutcheon or the
special “thread-on” escutcheon.  This
feature allows removal of ceiling panels
for easy access to ceiling equipment
without taking the system out of service
to remove the sprinkler.

Operation: A fusible alloy is sealed into
a bronze actuating rod (center strut) by
a stainless steel ball.  When the alloy
melts at its rated temperature, the ball is
forced upward into the center strut,
releasing the two ejectors and operating
the sprinkler.

WARNING

The Model H Recessed Pendent
Sprinklers described herein must be
installed and maintained in compliance
with this document, as well as with the
applicable standards of the National

Technical
Data

CENTRAL

      H

2-01

Standard Spray
Recessed
Pendent
Sprinklers

OBSOLETE