2

Figure 1 Model A-1

Adjustable Dry Pendent

Flush, Recessed

Figure 2 Model A-1

Adjustable Dry Pendent

Extended

Figure 3 Model A-1

Adjustable Dry Pendent

Concealed

Center Line of

Sprinkler Branch Line

Finished Ceiling

LIne

1"  (25 mm)

NPT

“C”

Dimension

(order length)

Center Line of

Sprinkler Branch

Line

1 1/2" (38.1 mm)

Min.

2" (50.8 mm)

Max.

2 9/16"

(65.1 mm)

Ceiling

Escutcheon

Plate

Main Tube

1" (25.4 mm), 1 1/4" (31.8 mm),

1 1/2" (38.1 mm)

Threaded Line Fitting = 3" (76.2 mm)
2" (50.8 mm) Threaded Line Fitting =

3 1/8" (79.4 mm)

Order “C”

 Dim.

K-Factor

*5" (127.0 mm)

5.35

6

1

4

" (158.8 mm)

5.32

7

1

2

" (190.5 mm)

5.29

8

3

4

" (222.3 mm)

5.26

10" (254.0 mm)

5.23

11

1

4

" (285.8 mm)

5.20

12

1

2

" (317.5 mm)

5.17

13

3

4

" (349.3 mm)

5.14

15" (381.0 mm)

5.11

16

1

4

" (412.8 mm)

5.08

17

1

2

" (444.5 mm)

5.05

18

3

4

" (476.3 mm)

5.02

20" (508.0 mm)

4.99

*  Available in flush only.

Recessed

K-Factor Table

Order “C”

Dim.

K-Factor

21

1

4

" (539.8 mm)

4.96

22

1

2

" (571.5 mm)

4.93

23

3

4

" (603.3 mm)

4.90

25" (635.0 mm)

4.87

26

1

4

" (666.8 mm)

4.84

27

1

2

" (698.5 mm)

4.81

28

3

4

" (730.3 mm)

4.78

30" (762.0 mm)

4.75

31

1

4

" (793.8 mm)

4.72

32

1

2

" (825.5 mm)

4.69

33

3

4

" (857.3 mm)

4.66

35" (889.0 mm)

4.63

Order “C”

Dim.

K-Factor

20" (508.0 mm)

4.88

21

1

4

" (539.8 mm)

4.85

22

1

2

" (571.5 mm)

4.82

23

3

4

" (603.3 mm)

4.79

25" (635.0 mm)

4.76

26

1

4

" (666.8 mm)

4.73

27

1

2

" (698.5 mm)

4.70

28

3

4

" (730.3 mm)

4.67

30" (762.0 mm)

4.64

31

1

4

" (793.8 mm)

4.61

32

1

2

" (825.5 mm)

4.58

33

3

4

" (857.3 mm)

4.55

35" (889.0 mm)

4.52

Extended

K-Factor Table

 Order “C”

Dim.

K-Factor

3

3

4

" (95.3 mm)

5.27

5" (127.0 mm)

5.24

6

1

4

" (158.8 mm)

5.21

7

1

2

" (190.5 mm)

5.18

8

3

4

" (222.3 mm)

5.15

10" (254.0 mm)

5.12

11

1

4

" (285.8 mm)

5.09

12

1

2

" (317.5 mm)

5.06

13

3

4

" (349.3 mm)

5.03

15" (381.0 mm)

5.00

16

1

4

" (412.8 mm)

4.97

17

1

2

" (444.5 mm)

7.94

18

3

4

" (476.3 mm)

4.91

Caution: This unit must only be installed with
the special cast iron fitting supplied, as this is a
listed assembly. Installation into any other
fitting will void the listing.

Notes:
A-1 Adjustable Dry Pendent Ordering Length

1.  Order by “C” Dimensions shown in the tables above.  Round

actual “C” dimension up or down to the closest “C” dimension
shown in the chart.  Field adjustment is 

±

1 1/2" (38.1 mm) from

the “C” dimension shown in the chart.  The “C” dimension is
measured from the center line of the branch line to the face of
the finished ceiling.

2.  Maximum Listed length is 36" (914.4 mm).

A-1 Adjustable Dry Pendent Design Guidelines
After determining the order length, use the K-factor associated with
the length in the hydraulic calculations at the tee in the branchline.

Concealed

K-Factor Table

Order “C”

Dim.

K-Factor

22

1

2

" (571.5 mm)

4.93

23

3

4

" (603.3 mm)

4.90

25" (635.0 mm)

4.87

26

1

4

" (666.8 mm)

4.84

27

1

2

" (698.5 mm)

4.81

28

3

4

" (730.3 mm)

4.78

30" (762.0 mm)

4.75

31

1

4

" (793.8 mm)

4.72

32

1

2

" (825.5 mm)

4.69

33

3

4

" (857.3 mm)

4.66

35" (889.0 mm)

4.63

Order “C”

 Dim.

K-Factor

7

1

2

" (190.5 mm)

5.29

8

3

4

" (222.3 mm)

5.26

10" (254.0 mm)

5.23

11

1

4

" (285.8 mm)

5.20

12

1

2

" (317.5 mm)

5.17

13

3

4

" (349.3 mm)

5.14

15" (381.0 mm)

5.11

16

1

4

" (412.8 mm)

5.08

17

1

2

" (444.5 mm)

5.05

18

3

4

" (476.3 mm)

5.02

20" (508.0 mm)

4.99

21

1

4

" (539.8 mm)

4.96

Center Line of

Sprinkler Branch Line

Finished Ceiling

LIne

“C”

Dimension

(order length)

Center Line of

Sprinkler Branch

Line

3 3/4" (95.3 mm) Min.
4 5/8  (117.5 mm) Max.

Main Tube

1" (25.4 mm), 1 1/4" (31.8 mm),

1 1/2" (38.1 mm)

Threaded Line Fitting = 3" (76.2 mm)
2" (50.8 mm) Threaded Line Fitting =

3 1/8" (79.4 mm)

1"  (25 mm)

NPT

2 9/16"

(65.1 mm)

Center Line of

Sprinkler Branch Line

Finished

Ceiling LIne

Main Tube

Center Line of

Sprinkler Branch

Line

Ceiling Cover Plate

3 5/8" (92.1 mm) Diameter

“C”

Dimension

(order length)

3/16"

(4.8 mm)

1" (25.4 mm), 1 1/4" (31.8 mm),

1 1/2" (38.1 mm)

Threaded Line Fitting = 3" (76.2 mm)
2" (50.8 mm) Threaded Line Fitting =

3 1/8" (79.4 mm)

2 9/16"

(65.1 mm)

1"  (25 mm)

NPT

OBSOLETE