©1994 Central Sprinkler Company
Printed in U.S.A.
Central’s Sprinkler Head Cabinet is
designed with two
3
⁄
16
" diameter holes
for wall mounting or direct attachment
to the system riser with a strap-type
hanger. The Cabinet should be
installed at or near the system control
valve and must be stocked with an
adequate supply of spare sprinklers
and a sprinkler wrench.
The stock of spare sprinklers
should include sprinklers of each type
and temperature rating as are
installed in the sprinkler system, in
the following quantities:
Sprinklers
Spare Sprinklers
In System
Required
under 300
6
300-1000
12
over 1000
24
The Cabinets are designed to
accept both
1
⁄
2
" and
3
⁄
4
" N.P.T.
threaded sprinklers. For
1
⁄
2
" N.P.T.
sprinklers, leave the removable
knockout in the hole. For
3
⁄
4
" N.P.T.
sprinklers, insert a screwdriver blade
from the front top of the shelf and
under the near bottom part of the
knockout annular ring. Press the
screwdriver handle down to remove
the knockout ring. The hole, with the
knockout ring removed, will accept a
3
⁄
4
" N.P.T. sprinkler.
When placing an order, indicate the
full product name. Please specify the
quantity, model, style, capacity, and
size.
Sprinklers, wrenches, and hard-
ware for hanging are not supplied
with the Cabinet. They must be
ordered separately.
Availability and Service: Central
sprinklers, accessories, and other
products are available throughout the
U.S. and Canada, and internationally
through a network of Central
Sprinkler distribution centers. You
may write directly to Central Sprinkler
Company, or call (215) 362-0700 for
the distributor nearest you.
Guarantee: Central Sprinkler
Company will repair and/or replace
any products found to be defective in
material or workmanship within a
period of one year from date of
shipment. Please refer to the current
Price List for further details of the
warranty.
Conversion Table:
1 inch = 25.400 mm
1 foot = 0.3048 M
1 pound = 0.4536 kg
Conversions are approximate.
Central Sprinkler Company
451 North Cannon Avenue, Lansdale, PA 19446
Phone (215) 362-0700
FAX (215) 362-5385
Hd.Cab.2
Ordering
Information
Installation
Care &
Maintenance
The Cabinet, wrench, and stock of
spare sprinklers should be inspected
at least quarterly. The following items
should be checked:
1. The Cabinet should be readily
accessible, and not exposed to
a corrosive atmosphere or
temperatures in excess of
100
o
F/38
o
C.
2. The stock of spare sprinklers
should include an adequate
number of each type and
temperature rating.
3. The stock of sprinklers must be
in good condition.
4. A sprinkler wrench of the
appropriate type must be
included in the Cabinet.
OBSOLETE