408-8908

SOLISTRAND Flag Terminal Crimping Dies

3 of 6

Rev O

Wire Barrel

Crimped

Flag Terminal

Die Set

Terminal

Strip Length

Hydraulic Head (Typical)

PRODUCT

NOMINAL WIRE SIZE

STRIP LENGTH

PRODUCT

MM

2

AWG

MINIMUM

MAXIMUM

696775-1

696779-1

7-8

8

9.53 [.375]

11.18 [.440]

322727-[ ]

321576

13-15

6

12.70 [.500]

14.27[.562]

321060

21

4

13.82 [.554]

15.48 [.609]

321064

34-35

2

17.06 [.672]

18.65 [.734]

321066

59-60

1/0

22.23 [.875]

23.81 [.937]

321584

67-70

2/0

23.81 [.937]

25.40 [1.000]

327887

80-95

3/0

26.98 [1.062]

28.58 [1.125]

321259-[ ]

100-125

4/0

28.58 [1.125]

30.16 [1.187]

Figure 3

Figure 4

Hydraulic Head (Typical)

Center Terminal

Wire Barrel in Nest

Hold Flag Terminal

Tongue Against

Slope on Nest Until

Crimp is Started

5. MAINTENANCE AND INSPECTION

Disconnect power supply before performing

maintenance, adjustments, inspections, and

repairs.

5.1. Crimp Inspection

(Figure 5)

Inspect crimped terminals by checking the features
described in Figure 5. Use only terminals that meet
the conditions shown in the ACCEPT column.
Terminals displaying the features shown in the
REJECT column can be avoided by careful use of
these instructions and by performing the maintenance
and inspection procedures described in Paragraphs
5.2 and 5.3.

5.2. Daily Maintenance

It is recommended that each operator of the dies be
made aware of, and responsible for, the following steps
of daily maintenance.

DANGER