8

Outlet Temperature Adjustment Range

30˚C to 50˚C

Temperature Stability

±2˚C

Maximum Hot Inlet Temperature

85˚C

DO8 Working Pressure Range

1.0 to 5.0 bar : High Pressure

Min Temp Differential (Mix to Hot) for Fail-Safe

10˚C

Max. Pressure Inlet Differential

5 : 1

Sola TMV3 Thermostatic Basin Tap

Introduction

The Sola safe touch thermostatic basin tap has been specifically designed and manufactured to
meet the requirements of BS 7942: 2000 and NHS D08. The valve has been independently
tested and approved as a TYPE 3 valve under the TMV3 scheme.

Technical Specification / Conditions for use TMV3 Valves

NOTE:

Valves operating outside these conditions cannot be guaranteed by the Scheme to

operate as Type 3 valves.

Approvals

   TMV3 Scheme Approval Number:                      Details Available on Request

   WRAS Scheme Approval Number:                    Details Available on Request

Fail Safe Function

The Sola thermostatic basin tap is designed to stop the mixed water flow in the event of either the
hot or cold water supply failing when installed in accordance with these instructions. To ensure full
closure of the mixed water flow the minimum temperature differential between the hot water inlet
to the tap and the mixed water outlet 

MUST be at least 10˚C.

Operating Pressure Range

High Pressure

Low Pressure

Maximum Static Pressure 

10 bar   

10 bar

Flow Pressure, Hot and Cold

1 to 5 bar

0.2 to 1 bar

Hot Supply Temperature

55˚C to 65˚C

55˚C to 65˚C

Cold Supply Temperature

5˚C to 20˚C

5˚C to 20˚C

Содержание SF1139CP

Страница 1: ...e We cannot accept any responsibility should it be found that in any respect the information is inaccurate or incomplete or becomes so as a result of further developments or otherwise Twyford Bathroom...

Страница 2: ...ge Introduction and Safety 2 Components 3 Technical Data 4 Dimensions 4 Installation 5 Calibration 6 Cartridge Replacement 7 Aftercare and Spout Removal 7 TMV3 Section Introduction 8 Technical Specifi...

Страница 3: ...re optimum performance levels of the product are obtained Safety Twyford thermostatic basin taps must be installed and commissioned correctly to ensure that water is supplied at a safe temperature to...

Страница 4: ...Handle 8 2 Temperature stop ring 9 1 Thermostatic cartridge 10 1 Seat 11 1 Sealing ring 12 1 Horse shoe plate 13 1 Threaded rod 14 1 Retaining nut 15 2 350mm copper tail integral with body 16 2 Check...

Страница 5: ...le for non modulating combination boilers Max Inlet Pressure Static 12 bar Max Unbalanced Pressure Ratio 15 1 Max Inlet Pressure Dynamic 5 bar with flow regulator Max Inlet Temperature 85 C Max Unbala...

Страница 6: ...tube Screw the threaded rod 13 into the threaded hole in the base of the body taking care not to over tighten The cold supply must be connected to the right hand side and the hot to the left hand side...

Страница 7: ...e cartridge Temporarily refit the handle 7 Using a digital thermometer increase or reduce the mixed water outlet temperature until 38 C is established and stabilised Remove the handle 7 and refit the...

Страница 8: ...ubricate the O ring with a WRAS approved silicone based grease Re assemble in the reverse order Twyford taps have a high quality finish and should be treated with care An occasional wipe with a mild w...

Страница 9: ...de these conditions cannot be guaranteed by the Scheme to operate as Type 3 valves Approvals TMV3 Scheme Approval Number Details Available on Request WRAS Scheme Approval Number Details Available on R...

Страница 10: ...um temperature position vi Refit the handle in the reverse order Installation IMPORTANT The following instructions must be read prior to the installation of any Sola basin tap The installer should als...

Страница 11: ...s are excessive it is possible to fit a pressure reducing valve or a flow regulator to reduce the pressure s to within the limits as quoted previously 8 Any thermostatic basin tap must be fitted with...

Страница 12: ...e supply as the basin tap are opened during the setting of the mixed water temperature During commissioning it is advisable to ensure that the water temperatures are established before any attempt to...

Страница 13: ...esetting the mixed water temperature check that 2 1 All the strainers are clean 2 2 All the check valves are in good working order 2 3 The isolation valves are fully open 3 If the mixed water temperat...

Страница 14: ...th of these periods necessitating adjustment of the mixed water temperature then the next in service test can be deferred to 18 to 21 weeks after commissioning 6 4 If significant changes e g 2 K in th...

Страница 15: ...ome nishes components such as lters seals O rings and washers Incorrect installation Repair using non Twyford parts Accidental or wilful misuse Corrosion and the use of inappropriate cleaning products...

Страница 16: ...E O E 05 07 18 Twyford Lawton Road Alsager Stoke on Trent ST7 2DF UK UK Technical Helpline Telephone 01926 516800 or 01270 879777 Email technical geberit co uk Website www twyfordbathrooms com...

Отзывы: