Calibration

The Sola Safe Touch mixer tap has a factory set outlet temperature of 38˚C via the security 
setting. This is based on a balanced supply pressure and a stable hot water inlet temperature 
of 65˚C.

However, the calibration point MUST be checked and re-set as necessary to suit site 
conditions.

Care must be taken when re-calibrating the tap as INCORRECT CALIBRATION CAN CAUSE 
INJURY.

   •   Remove the indice (5), retaining screw (6), handle (7).

• Remove both rings (A & B) from the cartridge. 

• Temporarily refit the handle (7).

• Using a digital thermometer increase or reduce the mixed water outlet temperature until 38˚C

is established and stabilised.

•  Remove the handle (7) and refit the temperature stop rings (A) as shown in Fig 1 onto 

the splined section of the cartridge at the maximum temperature position.

• Temporarily refit the handle (7) and rotate clockwise until the water flow stops, refit 

temperature stop ring (B) as shown in Fig 2.

• Refit the handle in the reverse order.

•  Check calibration temperature.

PLEASE NOTE THAT ONCE CALIBRATED, THE SECURITY SETTING WILL ONLY BE 38˚C 
UNDER THE SUPPLY CONDITIONS USED FOR CALIBRATION.

B - Cold

A

B

A - Hot

Fig. 1

Fig. 2

Содержание SF1139CP

Страница 1: ...e We cannot accept any responsibility should it be found that in any respect the information is inaccurate or incomplete or becomes so as a result of further developments or otherwise Twyford Bathroom...

Страница 2: ...ge Introduction and Safety 2 Components 3 Technical Data 4 Dimensions 4 Installation 5 Calibration 6 Cartridge Replacement 7 Aftercare and Spout Removal 7 TMV3 Section Introduction 8 Technical Specifi...

Страница 3: ...re optimum performance levels of the product are obtained Safety Twyford thermostatic basin taps must be installed and commissioned correctly to ensure that water is supplied at a safe temperature to...

Страница 4: ...Handle 8 2 Temperature stop ring 9 1 Thermostatic cartridge 10 1 Seat 11 1 Sealing ring 12 1 Horse shoe plate 13 1 Threaded rod 14 1 Retaining nut 15 2 350mm copper tail integral with body 16 2 Check...

Страница 5: ...le for non modulating combination boilers Max Inlet Pressure Static 12 bar Max Unbalanced Pressure Ratio 15 1 Max Inlet Pressure Dynamic 5 bar with flow regulator Max Inlet Temperature 85 C Max Unbala...

Страница 6: ...tube Screw the threaded rod 13 into the threaded hole in the base of the body taking care not to over tighten The cold supply must be connected to the right hand side and the hot to the left hand side...

Страница 7: ...e cartridge Temporarily refit the handle 7 Using a digital thermometer increase or reduce the mixed water outlet temperature until 38 C is established and stabilised Remove the handle 7 and refit the...

Страница 8: ...ubricate the O ring with a WRAS approved silicone based grease Re assemble in the reverse order Twyford taps have a high quality finish and should be treated with care An occasional wipe with a mild w...

Страница 9: ...de these conditions cannot be guaranteed by the Scheme to operate as Type 3 valves Approvals TMV3 Scheme Approval Number Details Available on Request WRAS Scheme Approval Number Details Available on R...

Страница 10: ...um temperature position vi Refit the handle in the reverse order Installation IMPORTANT The following instructions must be read prior to the installation of any Sola basin tap The installer should als...

Страница 11: ...s are excessive it is possible to fit a pressure reducing valve or a flow regulator to reduce the pressure s to within the limits as quoted previously 8 Any thermostatic basin tap must be fitted with...

Страница 12: ...e supply as the basin tap are opened during the setting of the mixed water temperature During commissioning it is advisable to ensure that the water temperatures are established before any attempt to...

Страница 13: ...esetting the mixed water temperature check that 2 1 All the strainers are clean 2 2 All the check valves are in good working order 2 3 The isolation valves are fully open 3 If the mixed water temperat...

Страница 14: ...th of these periods necessitating adjustment of the mixed water temperature then the next in service test can be deferred to 18 to 21 weeks after commissioning 6 4 If significant changes e g 2 K in th...

Страница 15: ...ome nishes components such as lters seals O rings and washers Incorrect installation Repair using non Twyford parts Accidental or wilful misuse Corrosion and the use of inappropriate cleaning products...

Страница 16: ...E O E 05 07 18 Twyford Lawton Road Alsager Stoke on Trent ST7 2DF UK UK Technical Helpline Telephone 01926 516800 or 01270 879777 Email technical geberit co uk Website www twyfordbathrooms com...

Отзывы: