5
Installation
Securely mount the heater before wiring.
WARNING
: THE INLET AIR/GAS SIDE OF THE HEATER IS LOCATED CLOSEST TO WHERE THE
POWER LEAD CONNECTIONS ARE MADE. INSTALLING THE HEATER IN THE WRONG ORIENTATION
WILL DAMAGE THE HEATER AND CAN CREATE ADDITIONAL HAZARDS AS A RESULT.
1.
Securely mount the heater. Do not clamp so tightly as to distort the stainless steel housing.
2.
Connect the filtered air source to the heater using ¼” ID high pressure tubing.
3.
Connect the two power leads, grounding screw, and thermocouple leads to the appropriate connections. For
“K” thermocouples, the red lead is negative (-), and the yellow lead is positive (+).
4.
If a thermocouple is used external to the heater, ensure that it is located within one inch from the heater exit.
Typical Wiring for Hot Air Tools with Closed Loop Control