(17E000) Close
(17E001) Open (default)
User Manual
Authentication in
Turnstile
Lane (15EXXX)
Will allow user verification while the IR sensors are triggered.
Delay between successful user authentication and swing-barrier opening
(18EXXX)
Program the time delay between successful user authentication and when
OMD22
swing barriers will open
.
Time delay can be programmed
between 1 and
60
seconds
, and the default value is 2s.
Pedestrian Permitted Time in Turnstile Lane
(19EXXX)
Program how long a pedestrian is permitted to remain in the turnstile lane before
OMD22
triggers an alarm.
Duration Time can be
programmed
between 5 to 30
seconds
and the default value is 10s.
Volume Setting (16EXXX)
Volume Setting is used for adjusting the volume of
OMD22
audio alerts
. The
higher
the
number is
programmed
, the louder the volume.
The Volume Setting can
be programmed between 1 to 100 and the default value is 0.
Disable
Alarm (17EXXX)
When the alarm is disabled,
OMD22
will not trigger an alarm, regardless the
situation.
(15E000) Allow (default)
(15E001) Forbidden