Step 2 

______________

C

____________________________________________________________________________________________________________ 

04/21/05

 

Rev. A

 

940-00012-003 

 

 

Install Office Wiring 

 

A

 

Connect Office

Battery.

 

Connect "A" and/or "B" 
-48V at the rear of the 
TransAccess 155 shelf.  
(Refer to Chapter 2 in 
the Operations Manual. 

 

 

Use up to 12 gauge wire 
(14 gauge recommended). 

 

 

Do not turn the power on. 

 
 

 

B

 

Connect Office

Alarms.

 

Connect Minor, Major, 

and Critical alarms at 
the rear of the 
TransAccess 155 shelf. 

 

 

Use up to 18 gauge 
wire. 

 

 

Common, Normally-open,  and Normally-closed contacts are provided. 

 

 

See Chapter 2 of the Operations Manual for more details. 

 
 
 
 
 
 

__

Содержание TransAccess 155

Страница 1: ...se of the TransAccess 155 This Quick Start Guide describes the steps necessary to unpack install and initialize your new equipment It is strongly recommended that you read this entire document before proceeding This document is supplemental to the full Operations Manual for the TransAccess 155 ______________________________________________________________ ...

Страница 2: ...l items against the packing list B The shelf mounting ears may already be attached For the flush mounting option reverse the ears per Section 2 2 of the Operations Manual Install the shelf mounting ears ____________________________________________________________________________________________________________________________ 04 21 05 Rev A 940 00012 003 ...

Страница 3: ...t it matches the mounting space boundaries on the rack All 4 holes must line up Use four 12 24 screws Leave space above and below the TransAccess 155 if airflow would otherwise be restricted ____________________________________________________________________________________________________________________________ 04 21 05 Rev A 940 00012 003 ...

Страница 4: ... and or B 48V at the rear of the TransAccess 155 shelf Refer to Chapter 2 in the Operations Manual Use up to 12 gauge wire 14 gauge recommended Do not turn the power on B Connect Office Alarms Connect Minor Major and Critical alarms at the rear of the TransAccess 155 shelf Use up to 18 gauge wire Common Normally open and Normally closed contacts are provided See Chapter 2 of the Operations Manual ...

Страница 5: ...mbly part number 815 00089 XXX D Connect the fiber port Connect the customer supplied fiber cables to the fiber ports of the OMX84 module ____________________________________________________________________________________________________________________________ 04 21 05 Rev A 940 00012 003 ...

Страница 6: ...le All the LEDs in the shelf should illuminate less B Connect the User Interface Device UID Connect the User Interface Device UID customer supplied PC or Terminal to the User System Interface USI port on the OMX84 Module Note the UID may be connected to either OMX84 module Use Turin Networks cable 815 00011 XXX See Chapter 4 of the Operations Manual for more information ___________________________...

Страница 7: ..._____________________________________ 04 21 05 Rev A 940 00012 003 Select CONFIG at the top level menu If Remote Management is required select IP SNMP DCC in the drop down menu Set the IP Address and Gateway for Telnet SNMP and DCC Operation Move the cursor to the IP Address Netmask and Gateway locations and enter the information S to save E From the Main Menu select CONFIG then LINE Configure the...

Страница 8: ... the space bar to toggle each selection If a T1 port LBO is not selected the T1 port will be disabled and input alarms will not be reported for that tributary G Connect appropriate test sets to the T1 and or OC 3 facility connections Verify integrity of the circuits Verify error free transmission through each OMX84 service module If errors occur check the configuration and retest Turin Networks In...

Отзывы: