![turck TX700FB Скачать руководство пользователя страница 17](http://html1.mh-extra.com/html/turck/tx700fb/tx700fb_instructions-for-use-manual_1181791017.webp)
V01.00 | 2020/11
17
5.4
Grounding the device
Connect terminal 3 of the supply connector to the ground terminal.
General instructions for device grounding
All the electronic devices in the control system must be properly grounded.
Carry out grounding according to the applicable regulations.
Ground the device to minimize noise effects from electromagnetic interference.
Ground the unit via the grounding screw near the power supply connection.
Grounding the power supply
The power supply circuit may be floating or grounded.
To ground the supply circuit, connect the ground wire to the protective earth as shown
in the following figure (dotted line).
If the supply circuit is not grounded, the unit itself is internally connected to ground
(1 MΩ resistor with 4.7 nF capacitor connected in parallel).
The power supply must have double or reinforced insulation.
Fig. 9: Power supply – wiring