8
Operating
CAUTION
Operating the device outside the specification
Slight injuries and equipment damage possible.
Operate the unit only within the operating temperature specified in the tech-
nical data.
Use only thermally suitable connection cables.
8.1
LED displays
The device has the following LED indicators:
n
IO-Link communication
n
I/O status
8.1.1
IO-Link
IO-Link LED
Meaning
Green flashing
(1 Hz)
IO-Link communication OK, valid process data are sent
Red
IO-Link communication error or module error
Red flashing
(1 Hz)
IO-Link communication OK, invalid process data or diagnostic message
Off
No voltage supply
8.1.2
Channel-LEDs
LED C1 A/B…C8 A/B
Meaning
Green
Input active
Off
Input inactive
8.2
IO-Link events
Event
Code
Description
Event Mode
0x5000 Hardware error
0xF4 (appears)
0xB4 (disappears)
0x5110 Overvoltage
0xF4 (appears)
Overvoltage at supply
0xB4 (disappears)
0x5111 Undervoltage
0xF4 (appears)
Undervoltage at supply
0xB4 (disappears)
0x7710 Overcurrent
0xF4 (appears)
Group event:
Overcurrent of the sensor supply at one of
the connectors (C1…C8)
0xB4 (disappears)