Setting

Settable functions and features

18

Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com

Parameter

Meaning

ISO 10816-3

The precise vibration limit values for industrial machinery are specified in the ISO
10816-3 standard. The vibration limit values are used to assess industrial 
machinery with a rated power of ≥15 kW and a rated speed of 120…1500 rpm.
Different values are given for machines with rigid or flexible mounting supports.
Configurable switching outputs with PNP/NPN logic can indicate values exceed-
ing the limit values defined in ISO 10816-3. The following limit value categories
apply:

n

Newly installed machine

n

Suitable for continuous operation

n

Permissible for short-time operation

n

Not permissible

The ISO 10816-3 classification consists of four groups of machines and pumps:

n

Group 1: Large machinery with a rated power between 300 kW and 50 MW or
an electric motor with ≤ 315 mm shaft height

n

Group 2: Medium-sized machinery with a rated power between 15 kW and
300 kW or an electric motor with 160 mm ≤ 315 mm shaft height

n

Group 3: Pumps with a rated power > 15 kW and an external drive

n

Group 4: Pumps with a rated power > 15 kW and an integrated drive

The classification of the machine supports into rigid and flexible systems is due
to the relationship of the natural frequency of the overall machine and support
system as well as the excitation frequency. If the lowest natural frequency of the
overall system is at least 25 % above the excitation frequency, the machine sup-
port is classified as rigid. Flexibly mounted machinery is dampened and more 
tolerant of vibration than rigidly mounted machinery, which is not dampened.
The following parameters can be set according to ISO-10816-3 grouping:

n

Group 1 rigid

n

Group 1 flexible

n

Group 2 rigid

n

Group 2 flexible

n

Group 3 rigid

n

Group 3 flexible

n

Group 4 rigid

n

Group 4 flexible

n

Temperature

n

Manual

Manual is used to manually define the limit values for the vibration speed in ms/s
and temperature at which the switching outputs are activated in the event of an
excess value.

Time slots

The rms values of the vibration speed, the acceleration or the peak-to-peak 
values are determined and output over the set period. The following time win-
dows for calculating the vibration can be defined:

n

20 ms

n

100 ms

n

250 ms

n

500 ms

n

1000 ms

Hysteresis

The hysteresis window of the switching outputs can be set as a percentage of the
configured threshold value.

Threshold values

When setting the limit values for vibration speed and temperature manually, it is
possible to set values for the pre-alarm and warning or alarm for each measure-
ment axis.

Содержание CMVT Series

Страница 1: ...Your Global Automation Partner Instructions for Use CMVT Condition Monitoring Sensors with IO Link...

Страница 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...

Страница 3: ...2 Properties and features 8 4 3 Operating principle 9 4 4 Functions and operating modes 9 4 4 1 IO Link mode 9 4 4 2 SIO mode standard I O mode 9 4 4 3 Measurement axes 9 4 4 4 Temperature measurement...

Страница 4: ...urck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 11 Maintenance 24 12 Repair 24 12 1 Returning devices 24 13 Disposal 24 14 Technical data 25 15 Turck subsidiaries contac...

Страница 5: ...m risk of death or severe injury if not avoided CAUTION CAUTION indicates a dangerous situation of medium risk which may result in minor or moderate injury if not avoided NOTICE NOTICE indicates a sit...

Страница 6: ...traight 0 3 RS4 30 cm cable M12 1 receptacle 4 pin straight CM VT Functional principle Detection type V Vibration T Temperature Condition Monitoring Sensors CM VT QR20 IOL X3 H1 1 4 1 2 2 Scope of del...

Страница 7: ...or condition monitoring or for predictive maintenance tasks The devices may only be used as described in these instructions Any other use is not in accord ance with the intended use Turck accepts no l...

Страница 8: ...6 2 46 Fig 1 Dimensions CMVT H1141 mm Inch 14 LED 3 5 5 0 22 42 5 1 67 52 2 05 62 6 2 46 20 0 79 M12 1 21 5 0 85 71 6 2 82 L Fig 2 Dimensions CMVT 0 3 RS4 4 1 1 Indication elements The devices are pr...

Страница 9: ...For this the device is integrated in the controller level via an IO Link master The communication parameters are exchanged first of all the cyclic data exchange of the process data process data objec...

Страница 10: ...0 F 49 208 4952 264 more turck com www turck com 4 4 4 Temperature measurement The condition monitoring sensors can output the temperature via acyclic data and cyclic data 16 bit telegrams The measure...

Страница 11: ...ink master channels protection type IP20 218 230 5 C4 C5 C6 C7 6 3 38 8 60 4 C0 C1 C2 C3 24 30 2 X2 X1 P2 P1 TBEN L4 8IOL 6814082 Compact multiprotocol I O module for Ethernet 8 IO Link master channel...

Страница 12: ...al PNP channels 0 5 A channel diagnostics protection type IP65 IP67 IP69K 42 11 5 15 M12 x 1 L M12 x 1 15 49 5 18 2 RKC4 4T 2 RSC4 4T TXL 6625608 Connection cable M12 female connector straight 4 pin M...

Страница 13: ...ement axes of the device to the direction of vibration Position the device as close as possible to the vibration source Clean the installation surface and the surrounding area Position the potted side...

Страница 14: ...6 Connection Connect the female connector of the connection cable to the male connector of the sensor Connect the open end of the connection cable to the power supply and or processing units 6 1 Wirin...

Страница 15: ...V01 01 2022 03 15 7 Commissioning After connecting and switching on the power supply the device is automatically ready for operation...

Страница 16: ...9 208 4952 264 more turck com www turck com 8 Operation 8 1 LED display LED Color Meaning PWR IOL Green Device is operational Green flashing IO Link communication active Out 1 Yellow Out 1 switching s...

Страница 17: ...n RMS in mm s n Peak to peak in mm s n RMS in g n Peak to peak in g The values are determined within set time windows and output cyclically The maximum value since the power supply was switched on can...

Страница 18: ...f the machine supports into rigid and flexible systems is due to the relationship of the natural frequency of the overall machine and support system as well as the excitation frequency If the lowest n...

Страница 19: ...parameter manual The Turck Vibration Monitor is also available for visualizing process data Access to the sensor parameters and the Turck Vibration Monitor requires the connection of a Turck IO Link...

Страница 20: ...bar of a local web browser default http 192 168 1 254 A login is required on the IO Link master in order to edit the settings via the web server and to call the Turck Vibration Monitor Enter the passw...

Страница 21: ...V01 01 2022 03 21 Load the device specific IODD into the web server via Load IODD Fig 10 Loading the IODD...

Страница 22: ...The process data is recorded over time in seconds The recorded process data is used for example to define warnings for the switching outputs or to determine the measurement axis with the largest vibra...

Страница 23: ...irst check whether ambient interference is present If there is no ambient interference present check the connections of the device for faults If there are no faults there is a device malfunction In th...

Страница 24: ...return acceptance conditions when returning the device to Turck 12 1 Returning devices Returns to Turck can only be accepted if the device has been equipped with a Decontamination declaration enclose...

Страница 25: ...lity 5 at 79 58 Hz Temperature Temperature measuring range 40 85 C Temperature linearity deviation 1 Temperature repeatability 2 4 Electrical data Operating voltage 18 30 VDC Ripple 10 Uss Insulation...

Страница 26: ...QR20 IOLX3 0 3 RS4 Ambient conditions Ambient temperature 40 85 C Temperature changes EN 60068 2 14 40 85 C Vibration resistance EN 60068 2 6 20 g 5 h axis 3 axes Shock resistance EN 60068 2 27 200 g...

Страница 27: ...MARNE LA VALLEE Cedex 4 www turckbanner fr Great Britain TURCK BANNER LIMITED Blenheim House Hurricane Way GB SS11 8YT Wickford Essex www turckbanner co uk India TURCK India Automation Pvt Ltd 401 40...

Страница 28: ...RCK RUS OOO 2 nd Pryadilnaya Street 1 105037 Moscow www turck ru Sweden Turck Sweden Office Fabriksstr ket 9 433 76 Jonsered www turck se Singapore TURCK BANNER Singapore Pte Ltd 25 International Busi...

Страница 29: ...Over 30 subsidiaries and over 60 representations worldwide www turck com 100031992 2022 03 100031992...

Отзывы: