D301087 1211 - BL20 CANopen
6-3
Random Module Arrangement
The following overview shows the maximum number of channels possible, on condition that the entire
station is made up of that respective type of channel only:
Further limitations can be placed on the maximum possible number of BL20 modules by the use of the
Power Feeding modules BL20-PF-24VDC-D or BL20-PF-120/230VAC-D; these being used either for
creating potential groups or by insufficient field supply.
Table 6-1:
Maximum system
extension
Channels
Modules
Type
Max. no.
Type
Max. no.
A
plus 1 Bus Ref-
reshing module
B
plus 2
Bus Refreshing
modules
C
plus 3
Bus Refreshing
modules
Digital inputs
288
BL20-4DI-24VDC-P
72
B
Digital outputs
288
BL20-4DO-24VDC-
0.5A-P
72
B
Analog inputs, current
126
BL20-2AI-I(0/4...20MA)
63
C
Analog inputs, voltage
126
BL20-2AI-U(-10/
0...+10VDC)
63
C
Analog inputs, voltage/
current
112
BL20-4AI-U/I
28
A
Analog inputs, PT /Ni
126
BL20-2AI-PT/NI-2/3
63
C
Analog inputs,
Thermocouple
126
BL20-2AI-THERMO-PI
63
C
Analog outputs,
current
126
BL20-2AO-I(0/4...20MA)
63
C
Analog inputs, voltage
126
BL20-2AO-U(-10/
0...+10VDC)
63
C
Counter
31
BL20-1CNT-24VDC
31
A
RS232
31
BL20-1RS232
31
A
RS485/422
31
BL20-1RS
485/422 3
1
A
SSI
31
BL20-1SSI
31
A
SWIRE
16
BL20-E-1SWIRE
16
A
Attention
Ensure that a sufficient number of Power Feeding or Bus Refreshing modules are used if the
system is extended to its maximum.
Note
If the system limits are exceeded, the software I/O-ASSISTANT gen-erates an error message
when the user activates the "Station
→
Verify" command.
Содержание BL20-GW-CANOPEN
Страница 1: ...BL20 USER MANUAL FOR CANopen...
Страница 4: ......
Страница 8: ...D301087 1211 BL20 CANopen iv...
Страница 14: ...About this Manual D301087 1211 BL20 CANopen 1 6...
Страница 24: ...BL20 Philosophy D301087 1211 BL20 CANopen 2 10...
Страница 54: ...BL20 Communication in CANopen D301087 1211 BL20 CANopen 5 2...
Страница 68: ...Guidelines for Station Planning D301087 1211 BL20 CANopen 6 14...
Страница 82: ...BL20 Approvals for Zone 2 Division 2 D301087 1211 BL20 CANopen 8 2...
Страница 83: ...D301087 1211 BL20 CANopen 8 3...
Страница 84: ...BL20 Approvals for Zone 2 Division 2 D301087 1211 BL20 CANopen 8 4...
Страница 85: ...D301087 1211 BL20 CANopen 8 5...
Страница 86: ...BL20 Approvals for Zone 2 Division 2 D301087 1211 BL20 CANopen 8 6...
Страница 92: ...Glossary D301087 1211 BL20 CANopen 9 6...
Страница 94: ...Index D301087 1211 BL20 CANopen 10 2...