Operating
Process output data
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com
V01.00 | 2022/09 | 24
Designation
Meaning
Undervoltage Vx 0
No diagnostics
1
Undervoltage of supply voltage V1, V2 or V
IOL
Connector diagnostics – overcurrent sensor supply
Overcurrent Cx
0
No diagnostics
1
Overload at the sensor/actuator supply at the connector. At mod-
ules with group diagnostics all connector-LEDs of the supply
group flash simultaneously in case of an error.
Channel diagnostics – overcurrent output
Overcurrent Cx
0
No diagnostics
1
Overcurrent at output or short-circuit
9.2
Process output data
Byte
no.
Bit offset
7
6
5
4
3
2
1
0
Outputs
0
C3P2
(B)
C3P4
(A)
C2P2
(B)
C2P4
(A)
C1P2
(B)
C1P4
(A)
C0P2
(B)
C0P4
(A)
1
C7P2
(B)
C7P4
(A)
C6P2
(B)
C6P4
(A)
C5P2
(B)
C5P4
(A)
C4P2
(B)
C4P4
(A)
Designation
Meaning
CxPy
0
Output inactive
1
Output active
Содержание BIL-L4-16DXP-AUX
Страница 1: ...Your Global Automation Partner Instructions for Use TBIP L 16DXP AUX I O Hub with IO Link...
Страница 4: ...Table of Contents Hans Turck GmbH Co KG T 49 208 4952 0 more turck com www turck com V01 00 2022 09 4...
Страница 32: ...Appendix Hans Turck GmbH Co KG T 49 208 4952 0 more turck com www turck com V01 00 2022 09 32...
Страница 35: ...Over 30 subsidiaries and 60 representations worldwide www turck com 100019421 2022 09 100019421...