Hybrid Inverter Series 3600/48 and 5000/48
Technical Data
https://www.turbo-e.com/
Technical Data
HYBRID INVERTER SERIES
3600/48
HYBRID INVERTER SERIES
5000/48
Battery input data
Battery type
Acid-Lead or Li-Ion
Battery Voltage range (V)
40V-60V
Imax Charge (A)
90A
120A
Imax Discharge (A)
90A
120A
Load curve
3 steps/equalization
External Temperature Sensor
Optional
Cycle Life
Self-adapting to BMS
Input data CC
Pmax CC (W)
4680W
6500W
Input range PV (V)
370V (100V-500V)
MPPT range (V)
125V-425V
Full charge range (V)
240V-425V
Startup voltage
150V
Max input current (A)
11A+11A
Nº MPPTs
2
Strings per MPPT
1 / 1
Output data CA
Nominal Power (W)
3600W
5000W
Max. Power (W)
3960W
5500W
Peak Power (Offgrid)
Twice the Nominal Power, 10S
Max. Back-Up Power (W)
5000W
Nominal CA output current (A)
15.7
21.7
Max. CA current (A)
18
25
Peak Current (A)
35A
Power factor
0.8-1
Output frequency and voltage
50/60Hz; 220/230/240Vac (single phase)
Grid type
Single phase
Harmonic distortion
THD<3% (line loading)<1.5%
Efficiency
Max. Efficiency
97.60%
European Efficiency
96.50%
MPPT Efficiency
99.90%
© Copyright 2020. All rights reserved. The specifications of the data sheet can be changed
without prior notice.
CAUTION: READ THE INSTRUCTION AND INSTALLATION MANUAL BEFORE USING THE PRODUCT.