and inadequate air flow may result.
Condensing units should be located away
from general public and the street.
Make sure units are kept horizontal.
Mounting Condensing Unit.
Mounting base should be concrete or
steel sufficient to support between 2 to 5
times the weight of condensing unit.
Condensing units must be mounted using
pads to avoid vibration or shifting.
The anchor bolts should be used to fix
the unit and tightened with spring washer
and nuts.
Spring Mounted Compressor.
Semi-hermetic compressor unit use the mounting assembly shown in Figure 11, the
shipping spacer is to be in place during shipment to insure maximum support for the
compressor body during transit.
Before the unit is put in operation, the shipping spacer should be removed and discarded.
Before operating the unit, it is necessary to follow these steps.
1.
Remove the upper nuts and washers.
2.
Remove and discard the shipping spacers.
3.
Install the rubber spacer. (rubber spacer tied to compressor.)
4.
Replace the upper mounting nuts and wahers.
5.
Allow 1/16” between the upper nut and the rubber spacer as Figure 11.
Figure 11. Spring Mount.