9. Displays and basic operation settings (cont.)
9.7 Menu 5 - Blowout temperature controller AIR (cont.)
Setback -WINTER ON
7 SELECT PARAMETER
1
5 Blowout temperature controller (AIR) menu 7
Setback -WINTER ON
7KHSUHGHÀQHGYDOXHRIDLUEORZRXWWHPSHUDWXUH
(menu 2) will be lowered in addiction of a outside sensor
exeeding a starting temperature (temporary outside tempera
ture e.g at noontime or at high solar radiation)
Setback -start °C
8 SELECT PARAMETER
21
5 Blowout temperature controller (AIR) menu 8
Setback -start °C
Outside sensor measure value (starting temperature) for
lowered air blow-out temperature
Setback -scaling
9 SELECT PARAMETER
10
5 Blowout temperature controller (AIR) menu 9
Setback -scaling
Skaling value for assignment of increasing temperary outside
temperature - to lowering blow-out temperature
(10 units matches 1° C, that means 1°C increasing
of outside temperature effects also a lowering
of blow-out temperature for 1°C)
Overwrite contr.valve
10 SELECT PARAMETER
0 %
0-100
5 Blowout temperature controller (AIR) menu 10
Overwrite control valve
Test facility: the setted valve opening for controller operation
will be overwritten time-limited by a test value (opening in %),
in this way the valve function can be tested.
The time-limitation for this function happens in the next menu.
Overwrite -time
11 SELECT PARAMETER
1
1-10
5 Blowout temperature controller (AIR) menu 11
Overwrite -time
Test facility: in connection with the above-mentioned menu
the valve function can be tested, this menu manages the
time limitation, afterwards reset to the controllers value