TTI QPX600D Скачать руководство пользователя страница 19

  

  18 

Output Protection 

In addition to OVP and OCP for forward over-voltage and over-current protection, the output is 
protected from reverse voltages by a diode; the continuous reverse current must not exceed  
3 Amps although transients can be much higher. 

Temperature Trip and Other Faults 

If the safe internal temperature limit is exceeded because, for example, the fan vents have been 
blocked, the output is automatically tripped off.  The display will show a message indicating that a 
fault has occurred and that the AC supply must be turned off and on again to reset the unit.  If 
over-temperature is suspected, the cause of the fault should be rectified and the unit allowed to 
cool before the AC supply is turned on again. 

Note that an over-temperature trip shuts down the primary side of the instrument and it is that 
condition that is detected and causes the fault message to be displayed.  However, other faults 
may occur which would also cause the primary side to shut down and these will not be 
distinguishable from an over-temperature trip. If the unit does not restart after being allowed to cool 
then another fault might be present and the unit should be returned for service. 

Logic Control Input and Output 

Digital signal connections LOGIC IN and LOGIC OUT are available on the rear panel; press the 
orange actuators of the screwless terminals, insert the connecting wire and release the actuator to 
secure the connection. LOGIC IN is connected directly to the input of an isolating opto-coupler; 
there is no series resistor. The input is active when an input current greater than approximately 
1mA is forced between LOGIC IN and LOGIC COMMON.  LOGIC IN can be set to enable the 
output, disable the output, or be ignored when it is activated, see the Extra Functions section. Note 
that LOGIC IN can only be used to enable/disable the output if the output has already been turned 
ON with the front panel 

 key or by remote interface command; this permits the front panel 

 

key to be used to turn the output off in an emergency, i.e. to override LOGIC IN.  Note also that, 
having turned the output ON with the 

 key, the ON lamp remains lit even when the output is 

disabled by the LOGIC IN signal. 

LOGIC OUT is an isolated rear-panel open-collector output that will sink up to 2mA when active 
(‘switch closure’); the maximum voltage that can be applied to LOGIC OUT is 30Vdc.  LOGIC OUT 
can be set to be ‘closed’ or ‘open’ for output enabled or disabled, current limit (CI mode), power 
limit (UNREG mode), or for any fault trip. The default condition is for LOGIC OUT to be ‘closed’ for 
the Output ON; loss of AC power, which would deactivate the opto, is also reliably detected with 
this setting. See Extra Functions section for further details. 

Analogue Control 

Rear panel connections V CONTROL and I CONTROL provide quasi-analogue control of the 
Output Voltage and Current Limit respectively.  The inputs are read 4 times per second by the  
A-to-D converter and the output is set according to the selected input scaling. The input scaling for 
both can be set as 0 to 10 Volts or 0 to 5 Volts for range maximum output. The Analogue Control 
functions and scaling are both selected from the keyboard, see Extra Functions section. 

The V CONTROL and I CONTROL inputs are differential, with a limited common mode range of  
± 2.5Vdc with respect to the negative output.  They should be driven from a ‘floating’ source such 
as another power supply. 

Analogue Control is activated from the Bus menu, see Remote Operation section.  When 
activated, the top line of the display shows which functions (V and/or I) have been selected and the 
corresponding functions on the front panel (NUMERIC SET / JOG SET for V and/or I ) are inhibited 
to avoid contention between Analogue Control and front panel operation. 

Analogue Monitor 

The output terminal voltage and output current may be monitored on V MONITOR and I MONITOR 
respectively.  The output scaling for both will be the same as that set for V CONTROL and I 
CONTROL, see above section.  V MONITOR and I MONITOR are always available at the rear 
panel terminals and should be connected to a measuring system with ‘floating’ inputs such as a 
DMM.  

Содержание QPX600D

Страница 1: ...QPX600D QPX600DP PowerFlex Dual DC Power Supplies INSTRUCTION MANUAL...

Страница 2: ...1 Manual Operation Independent Mode 13 Manual Operation Link Modes 21 Maintenance 22 Remote Operation 23 Remote Commands QPX600DP only 32 Note The latest revisions of this manual device drivers and so...

Страница 3: ...nt displayed when off Output Terminals Rear panel safety terminals accepting 6mm wire diameter 6mm plugs or 8mm spades at 50 Amps max or 4mm plugs at 30 Amps max Sensing Switchable between local and r...

Страница 4: ...t voltage and current These signals each have a range of 0 to 10V or 0 to 5V with respect to the shared COM return signal the set range applies to all inputs and outputs Analogue Control Voltage Range...

Страница 5: ...spectively RS232 Standard 9 pin D connector Baud rate 9600 USB Standard USB 2 0 hardware connection LAN Auto speed detect 10 100MHz Auto MDIX LXI V1 2 Class C compliant GPIB Conforms with IEEE488 1 an...

Страница 6: ...pean Communities EMC Emissions a EN61326 1 2006 Radiated Class A b EN61326 1 2006 Conducted Class A c EN61326 1 2006 Harmonics referring to EN61000 3 2 2006 Immunity EN61326 1 2006 Immunity Table 1 re...

Страница 7: ...ions 3m therefore not tested Performance A A signal lines were not tested on the basis that typical use will be with connections 3m for which there is no test requirement Immunity performance with con...

Страница 8: ...sion cord without a protective conductor When the instrument is connected to its supply terminals may be live and opening the covers or removal of parts except those to which access can be gained by h...

Страница 9: ...power rating information on the equipment or in the Specification WARNING THIS INSTRUMENT MUST BE EARTHED Any interruption of the mains earth conductor inside or outside the instrument will make the...

Страница 10: ...ons to the instrument with the OUTPUT off Logic Input each output LOGIC IN is connected directly to the input of an isolating opto coupler there is no series resistor The input is activated when a cur...

Страница 11: ...ccepts a standard USB cable The Windows plug and play functions should automatically recognise that the instrument has been connected If the correct driver is not found follow the Windows on screen pr...

Страница 12: ...s the default setting at power up Keypad Only the principles of operation are outlined here the setting of individual parameters is given in detail in later sections The paramount consideration in des...

Страница 13: ...s the maximum minimum settings in which case they are set to zero For example 59 861V goes to 59 961V goes to 60 000V for a 0 1V jog increment 1 60A goes to 0 60A goes to 0 01A for a 1A jog decrement...

Страница 14: ...er range the display will show UNREG unregulated and the actual output voltage will again be less than the set voltage The voltage can be set directly from the numeric keypad press the NUMERIC SET V k...

Страница 15: ...current entered with any remaining digits set to zero e g 1 2 3 OK will set 12 30A 1 OK will set 1 00A When OK is pressed the current limit is changed and the display reverts to the standard status m...

Страница 16: ...pressed the display shows the product of measured output voltage x measured current in the form nn n VA The V x A value is updated at the same measurement rate as for V and I Pressing ESCAPE cancels...

Страница 17: ...shows in the display beside the output status OFF CV CI or UNREG when remote sense is selected Remote sense is turned off by pressing SHIFT SENSE again the message Turn Off Remote Sense OK to confirm...

Страница 18: ...he OVP is tripped the display shows the message OVP Press ESC to Reset and the output is turned off Pressing ESCAPE at this point removes the message and the display now shows the preset voltage and c...

Страница 19: ...panel key to be used to turn the output off in an emergency i e to override LOGIC IN Note also that having turned the output ON with the key the ON lamp remains lit even when the output is disabled by...

Страница 20: ...y scrolling to the appropriate store number in the list using the JOG SET control the selected store is indicated by the square brackets at that location Press OK to recall the set up at the selected...

Страница 21: ...y default 41 V CONTROL only selected 42 I CONTROL only selected 50 V CONTROL and I CONTROL scaling 0 to 10 Volts factory default 51 V CONTROL and I CONTROL scaling 0 to 5 Volts 60 LOGIC IN ignored fac...

Страница 22: ...V2 must be 1V to enter this mode to permit the ratio to be determined with sufficient accuracy Track V I Show Total V To enter this mode both outputs must be off on entry the set points for V2 I2 and...

Страница 23: ...curing screws and lift off the cover Replace the fuse with one of the correct type and refit the cover Note that the main function of the fuse is to make the instrument safe and limit damage in the ev...

Страница 24: ...display to the standard status screen If Digital has been selected QPX600DP only pressing OK changes the display to show the current digital interface Address and the message Set Address with Jog Chan...

Страница 25: ...wever the effect of this action will only remain until the instrument is addressed again or receives another character from the interface when the remote state will once again be entered RS232 Interfa...

Страница 26: ...h time that instrument is subsequently connected the PC software makes use of the unique code embedded in each instrument to link it to the same virtual COM port irrespective of which physical USB por...

Страница 27: ...efault configuration is no password The Configure page itself explains how to set the password The password can be up to 15 characters long note that the User Name should be left blank The password wi...

Страница 28: ...nds though commands may be sent with a terminator if desired it will be ignored Each command over TCP behaves as if it is terminated with a command terminator ASCII character 0AH line feed GPIB Interf...

Страница 29: ...ll operation The instrument is configured by the controller sending a Parallel Poll Configure command PPC followed by a Parallel Poll Enable command PPE The bits in the PPE command are shown below bit...

Страница 30: ...is read and cleared using the EER command On power up this register is set to 0 for all interface instances Error messages have the following meaning 0 No error encountered 1 9 Indicates a hardware e...

Страница 31: ...ad either by the STB command which will return MSS in bit 6 or by a Serial Poll which will return RQS in bit 6 The Service Request Enable register is set by the SRE nrf command and read by the SRE com...

Страница 32: ...0 Query Error Register 0 Parallel Poll Enable Register 0 Registers marked thus are specific to the GPIB section of the instrument and are of limited use via other interfaces The instrument will be in...

Страница 33: ...ch is filled under interrupt in a manner transparent to all other instrument operations The queue contains raw un parsed data which is taken by the parser as required Commands and queries are executed...

Страница 34: ...off Once entered it is not possible to set V2 or I2 or turn the outputs on and off independently Output 2 will always match output1 Note This mode is useful if the outputs have been wired in parallel...

Страница 35: ...Return the set current limit of output n Response is I n nr2 rmt where nr2 is in Amps OVP n Return the voltage trip setting of output n Response is VP n nr2 rmt where nr2 is in Volts OCP n Return the...

Страница 36: ...t where nr1 is 1 for low range 0 to 60V and 2 for high range 0 to 80V CONFIG nrf Sets the configuration of the unit to nrf where nrf has the meaning defined in Operating Modes above CONFIG Returns the...

Страница 37: ...or the user has disabled the interface from taking control via the web interface IFUNLOCK Release the lock if possible Returns 0 if successful If this command is unsuccessful 1 is returned 200 is pla...

Страница 38: ...idgeshire PE29 7DR England United Kingdom Telephone 44 0 1480 412451 Fax 44 0 1480 450409 International web site www aimtti com UK web site www aimtti co uk Email info aimtti com Aim Instruments and T...

Отзывы: