26
5-3 Page3 Limit switch setting
1.
: SETUP channel selection
Same as Page 1.
2.
:
Limit
Switch ENA/DIS default : ENA
Set
independently in CW / CCW the enable or disable of the limit switch.
ENA: Motor will stop when it detects a signal limit.
DIS: Motor does not stop even if the detection limit signal.
3.
:
Contact
setting of the limit switch N.O/N.C default : N.O
Set i
ndependently CW / CCW the contact logic of the limit switch.
The right "_" will change to "
□
" When the limit switch is active.
N.O: Select when using the limit switch normally open (A contact).
N.C: S
elect when using the limit switch normally close (B contact).
4.
:
Selection
of stop mode: In case of limit switch
SLOW/FAST default: SLOW
Select from the FAST (Sudden stop) or SLOW (Deceleration stop) how to stop when
it
detects
a limit switch.
5.
:
Selection
of stop mode: In case of push button. (Panel operation)
SLOW/FAST default: SLOW
Select from FAST (Sudden stop) or SLOW (Deceleration stop) how to stop when
you push the STOP button in local mode.