![TSL MDU12-PMi Скачать руководство пользователя страница 13](http://html1.mh-extra.com/html/tsl/mdu12-pmi/mdu12-pmi_user-manual_1178341013.webp)
MDU12-PMi Manual
13
Issue 4
4.2
The Output Screen
All items in the boxes may be changed for this screen.
This is showing the individual status. The output names may be changed.
Individual circuits may be remotely switched on or off.
The Delay column figures are enabled by selecting Delay in the Mode check box on the System page.
This ranges from 0-256 seconds.
NB These delays are only effective on initial powering of the unit.
The SNMP Lock box if checked disables remote control access for that channel via SNMP protocol.
Press <<
Update
>> when done.
NB
Allow the page to refresh before cycling the power to check the settings.
Front Panel LED Indications:
•
LED
Indication
o
Power - Blue - Power applied to the unit.
o
LAN - Flashing Amber LAN connected & active
o
Output LEDs 1-12
o
Green - Circuit on and fuse OK
o
Amber – Circuit off and fuse OK.
o
Red – Circuit off and fuse failed.
o
Off – Circuit on but fuse has failed