Technical Section
29
Troubleshooting Section
The PresSura Room Pressure Monitor is designed to be trouble free. However,
installation problems or interaction with other HVAC components may cause system
problems. The PresSura system is easy to troubleshoot if an organized approach to
evaluate the system is taken. Troubleshooting is broken down into hardware and
software problems. Hardware problems deal with the physical installation of the device.
Hardware problems include wiring problems, incorrectly installed equipment, and add-
ons or non-TSI equipment. Software problems include configuration problems and
interaction problems with the HVAC system.
The hardware test described in this section determines that all TSI mechanical
components are functioning correctly. The hardware test requires the diagnostics menu
items to be accessed. If you are unfamiliar with the PresSura menus, see
Software
Programming
for keystroke procedure. Troubleshooting the majority of problems is
usually quick if the hardware test is followed.
Software and hardware problems are covered in the troubleshooting chart. Pick the
problem that most closely resembles your problem and review the possible symptoms
and corrective action. Software or system performance problems can and are affected by
the supply air system, exhaust air system, or physical configuration of the room.
Separating TSI system problems from the hospital HVAC system can sometimes be
difficult. TSI recommends confirming all hardware is operating correctly before
troubleshooting software problems.
Hardware Test
Three tests need to be performed in order to determine all hardware is functioning
correctly. The tests are broken down into:
Confirming wiring is correct.
Confirming physical installation is correct.
Verifying mechanical components.
Confirming wiring is correct.
The most common problem with installed hardware equipment is incorrect wiring. This
problem usually exists on initial installation, or when modifications to the system take
place. The wiring should be very closely checked to verify it
exactly
matches the wiring
diagram. The TSI cables are all color coded to ensure proper wiring. A wiring diagram is
located in
Appendix B
of this manual. Wiring associated with non TSI components should
be closely checked for correct installation. If non TSI components are installed, consider
disconnecting them for testing purposes.
Confirming physical installation is correct
All of the hardware components need to be installed properly. Review the installation
instructions and verify components are installed properly at the correct location. This is
easily done when the wiring is checked.
Verifying mechanical components
Verifying all TSI components are operating correctly requires following a simple
procedure. The fastest procedure to confirm all equipment is operating is to first test the
DIM, and then go into the diagnostic menu to test each component.
NOTE
: These tests require power to the units, so if unit has no power, refer to hardware
troubleshooting chart to eliminate power problem.
Содержание PRESSURA 8630-PM
Страница 2: ......
Страница 6: ...iv This page intentionally left blank...
Страница 44: ...Specifications 38 This page intentionally left blank...
Страница 45: ...Appendix B 39 Appendix B Wiring Diagram Figure 10 Wiring Diagram...
Страница 46: ...Wiring Diagram 40 This page intentionally left blank...
Страница 48: ...Access Codes 42 This page intentionally left blank...