Technical Section 

29 

Troubleshooting Section 

 
The PresSura Room Pressure Monitor is designed to be trouble free. However, 
installation problems or interaction with other HVAC components may cause system 
problems. The PresSura system is easy to troubleshoot if an organized approach to 
evaluate the system is taken. Troubleshooting is broken down into hardware and 
software problems. Hardware problems deal with the physical installation of the device. 
Hardware problems include wiring problems, incorrectly installed equipment, and add-
ons or non-TSI equipment. Software problems include configuration problems and 
interaction problems with the HVAC system.  
 
The hardware test described in this section determines that all TSI mechanical 
components are functioning correctly. The hardware test requires the diagnostics menu 
items to be accessed. If you are unfamiliar with the PresSura menus, see 

Software 

Programming

 for keystroke procedure. Troubleshooting the majority of problems is 

usually quick if the hardware test is followed. 
 
Software and hardware problems are covered in the troubleshooting chart. Pick the 
problem that most closely resembles your problem and review the possible symptoms 
and corrective action. Software or system performance problems can and are affected by 
the supply air system, exhaust air system, or physical configuration of the room. 
Separating TSI system problems from the hospital HVAC system can sometimes be 
difficult. TSI recommends confirming all hardware is operating correctly before 
troubleshooting software problems. 
 

Hardware Test  

Three tests need to be performed in order to determine all hardware is functioning 
correctly. The tests are broken down into: 
 
 

Confirming wiring is correct. 

 

Confirming physical installation is correct. 

 

Verifying mechanical components. 

 
Confirming wiring is correct. 
The most common problem with installed hardware equipment is incorrect wiring. This 
problem usually exists on initial installation, or when modifications to the system take 
place. The wiring should be very closely checked to verify it 

exactly

 matches the wiring 

diagram. The TSI cables are all color coded to ensure proper wiring. A wiring diagram is 
located in 

Appendix B 

of this manual. Wiring associated with non TSI components should 

be closely checked for correct installation. If non TSI components are installed, consider 
disconnecting them for testing purposes.  
 
Confirming physical installation is correct 
All of the hardware components need to be installed properly. Review the installation 
instructions and verify components are installed properly at the correct location. This is 
easily done when the wiring is checked. 
 
Verifying mechanical components 
Verifying all TSI components are operating correctly requires following a simple 
procedure. The fastest procedure to confirm all equipment is operating is to first test the 
DIM, and then go into the diagnostic menu to test each component. 
 

NOTE

:  These tests require power to the units, so if unit has no power, refer to hardware 

troubleshooting chart to eliminate power problem. 

Содержание PRESSURA 8630-PM

Страница 1: ...PRESSURA ROOM PRESSURE MONITOR MODELS 8630 SM 8630 PM OPERATION AND SERVICE MANUAL P N 1980242 REVISION G JUNE 2013...

Страница 2: ......

Страница 3: ...JUNE 2013 U S AND CANADA OTHER COUNTRIES Sales Customer Service Sales Customer Service 800 874 2811 651 490 2811 001 651 490 2811 Fax Fax 651 490 3824 001 651 490 3824 SHIP MAIL TO E MAIL TSI Incorpo...

Страница 4: ...MITED TO CLAIMS OF DIRECT INFRINGEMENT AND EXCLUDES CLAIMS OF CONTRIBUTORY OR INDUCED INFRINGEMENTS BUYER S EXCLUSIVE REMEDY SHALL BE THE RETURN OF THE PURCHASE PRICE DISCOUNTED FOR REASONABLE WEAR AN...

Страница 5: ...Sura unit functions and how to interface with the device This section should be read by users facilities staff and anyone who requires a basic understanding of how the PresSura controller operates Par...

Страница 6: ...iv This page intentionally left blank...

Страница 7: ...aff and other patients Conversely surgical areas and bone marrow patient rooms need positive room pressure air flowing out of the room to keep out contaminants that may adversely affect the patient Ro...

Страница 8: ...vates the alarms when necessary PresSura Room Pressure Controller is a continuous measuring system providing instant information on the room pressure Useful User Information The DIM has a green light...

Страница 9: ...ror messages In normal operation green light is on the display continuously scrolls information about room pressure and other variables programmed flow air changes per hour etc The variables that scro...

Страница 10: ...gram the audible alarm to be permanently turned off see AUDIBLE ALM AUX Key The AUX key is active only in specialty applications and is not used on the standard PresSura controller If the AUX key is u...

Страница 11: ...visual alarms activate The alarms turn off when set to unlatched when the unit returns to the safe range which is defined as negative pressure greater than 0 001 inches H2O Visual Alarm Operation The...

Страница 12: ...ion available prior to contacting your authorized TSI Manufacturer s Representative or TSI Model number of unit 8630 ____ Software revision level Facility where unit is installed First two items that...

Страница 13: ...including programming name description of menu of item range of programmable values and how the unit shipped from the factory default values This manual covers two models The features unique to the p...

Страница 14: ...haracters refer to Figure 4 are used to program or configure the unit to fit your particular application Programming the instrument will change how the unit functions so thoroughly review the items to...

Страница 15: ...erical specific properties on off or a bar graph NOTE When programming a menu item continuously pressing the arrow key will scroll through the values faster than if arrow key is pressed and released K...

Страница 16: ...ling room pressure flows etc Pressure is shown in this case PRESSURE 00085 H2O Press the MENU key to gain access to the menus MENU The first 2 menu choices are displayed ALARM CONFIGURE Press the SELE...

Страница 17: ...tle on the top line of the display and the menu item on the bottom line goes to step 3 ALARM POS LOW ALM WARNING If the MENU key was pressed instead of the SELECT key the new data would not have been...

Страница 18: ...ctory The menus covered in this section are divided into groups of related items to ease programming As an example all calibration items are in one menu alarm information in another etc The manual fol...

Страница 19: ...OM VOLUME 2 SENSOR ACCESS CODE CALIBRATION SENSOR ZERO SENSOR SPAN FLOW ZERO 2SENSOR ZERO 2SENSOR SPAN ELEVATION ACCESS CODE INTERFACE NET PROTOCOL NET ADDRESS OUTPUT RANGE OUTPUT SIG ACCESS CODE DIAG...

Страница 20: ...hen the TSI key switch is in negative room pressure position or when negative is selected in ROOM MODE item OFF 0 to 0 19500 H2O OFF POSITIVE LOW PRESSURE ALARM POS LOW ALM The POS LOW ALM item sets t...

Страница 21: ...ls below or goes in the opposite direction of the 2 LOW ALM set point The alarm can be a negative or positive pressure alarm set point The second sensor low and high alarms must be programmed for the...

Страница 22: ...the primary sensor or control sequence This alarm is on when the DIM is in positive or negative mode This item is enabled when the second pressure sensor item is enabled see menu item 2 SENSOR OFF 0 t...

Страница 23: ...alarm ACCESS CODE ACCESS CODE The ACCESS CODE item selects whether an access code pass code is required to enter the menu The ACCESS CODE item prevents unauthorized access to a menu If the ACCESS COD...

Страница 24: ...tivating the alarms This delay affects all alarms pressure and flow 7 The MUTE TIMEOUT item temporarily turns the audible alarm off for all pressure and flow alarms 8 The display can only show one ala...

Страница 25: ...in out of the room This item requires a TSI flow station to be mounted in the duct When a duct area is programmed the display will automatically scroll the actual flow as part of the display sequence...

Страница 26: ...dress must be set to 2 in order to function See Figure 9 to change second sensor address ON or OFF OFF ACCESS CODE ACCESS CODE The ACCESS CODE item selects whether an access code pass code is required...

Страница 27: ...he PresSura flow station pressure transducer A zero or no flow point needs to be established prior to using the flow measurement see Calibration section following menu item listing NONE Flow station p...

Страница 28: ...ELEVATION ELEVATION The ELEVATION item is used to enter the elevation of the hospital above sea level This item has a range of 0 to 10 000 feet in 1 000 foot increments The pressure value needs to be...

Страница 29: ...ange RS 485 communications allows you access to all menu items except calibration items The RS 485 network can initiate a change at any time The RS 485 cannot override the TSI key switch when ROOM MOD...

Страница 30: ...e analog output signal can either be 0 to 10 VDC or 4 to 20 mA 0 to 10 VDC or 4 to 20 mA 0 to 10 VDC ACCESS CODE ACCESS CODE The ACCESS CODE item selects whether an access code pass code is required t...

Страница 31: ...measurement Normally the velocity is checked at the crack under the doorway or the door is opened 1 to allow alignment of the air velocity probe making the measurement If the crack under the door is n...

Страница 32: ...ame direction both reads positive or negative This problem can only occur at very low pressures so slightly changing the balance should eliminate the problem Perform a smoke test to determine pressure...

Страница 33: ...hould be white and free of accumulated debris Figure 8 Pressure sensor door slid open Periodically inspect the other system components for proper performance and physical signs of excessive wear Press...

Страница 34: ...74 2811 U S and Canada or 001 651 490 2811 other countries or your nearest TSI Manufacturer s Representative for replacement part pricing and delivery Part Number Description 800244 Model 8630 SM Pres...

Страница 35: ...times be difficult TSI recommends confirming all hardware is operating correctly before troubleshooting software problems Hardware Test Three tests need to be performed in order to determine all hardw...

Страница 36: ...blow on sensor Displayed value should change If voltage changes the unit passes If voltage doesn t change proceed to Sensor status test TEST Sensor status Enter SENSOR STAT menu item in diagnostics me...

Страница 37: ...o not display on DIM except when SENSOR STAT item is selected The item will display NORMAL if communications are established correctly If problems exist one of four error messages will display COMM ER...

Страница 38: ...5 volts displayed equals 2832 ft min x duct area ft 2 Low Alarm Relay Menu Item LOW ALM REL The LOW ALM REL item is used to change the state of the low alarm relay When this item is entered the displa...

Страница 39: ...2 of DIM is 24 to 30 VAC If proper voltage is found between pins 1 and 2 of the DIM all wiring has been checked fuses have been reset and screen is still blank the DIM is probably defective Replace DI...

Страница 40: ...tch doesn t work Incorrect wiring Room mode is incorrect Defective switch defective DIM Verify wiring is correct between key switch and DIM Go into CONFIGURE menu ROOM MODE item Verify ROOM MODE is in...

Страница 41: ...ROTOCOL item The protocol must match host system Select correct interface The network address at the building automation system and at the DIM must match The network address must be unique for each DI...

Страница 42: ...ip the relay If relay responds contact opens and closes the device connected is incompatible or defective If relay doesn t respond relay is defective may be caused by incompatible device Replace DIM D...

Страница 43: ...ent 5A max voltage 150 VDC 250 VAC Minimum switch load 10 mA 5 VDC Contacts close in alarm condition Analog Output Type 0 to 10 VDC or 4 to 20 mA Range High 0 100 to 0 100 inches H2O Low 0 0100 to 0 0...

Страница 44: ...Specifications 38 This page intentionally left blank...

Страница 45: ...Appendix B 39 Appendix B Wiring Diagram Figure 10 Wiring Diagram...

Страница 46: ...Wiring Diagram 40 This page intentionally left blank...

Страница 47: ...essing the following key sequence will provide access to the required menu Key Setpoints Alarm Configure Calibration Control 1 EMERGENCY TEST EMERGENCY AUX MENU 2 MUTE TEST MENU MENU MUTE 3 MUTE MUTE...

Страница 48: ...Access Codes 42 This page intentionally left blank...

Страница 49: ...more information USA Tel 1 800 874 2811 UK Tel 44 149 4 459200 France Tel 33 4 91 11 87 64 Germany Tel 49 241 523030 India Tel 91 80 67877200 China Tel 86 10 8219 7688 Singapore Tel 65 6595 6388 P N 1...

Отзывы: