Part Two
62
Menu Item
Description
Setback Input
IN# NIGHT SETB
The
IN# NIGHT SETB
item reads the current state of a setback contact
input. This item will only be displayed when the corresponding
INPUT
SEL #
item has been set to
NIGHT SETB
under the
CONFIGURE
menu.
When this item is entered, the display will indicate either
OPEN
or
CLOSED
. If the display indicates
CLOSED
, the controller has been put
into setback mode through the contact input. If the display indicates
OPEN
, the controller has not been put into setback mode through the
contact input. However, the controller may be in setback mode if it has
been initiated through the keypad or via network communications.
NOTE:
IN# NIGHT SETB
is a read-only item.
Sash Position Input
IN1 SASH POS VER
The
IN1 SASH POS VER
item is used to read the input from the sash
position potentiometer. This item will only be displayed when the
INPUT
SEL 1 item has been set to
SASH POS VERT
under the
CONFIGURE
menu. When this item is entered, a voltage is indicated on the display.
The exact number displayed is relatively unimportant. More important is
that as the fume hood sash is moved, the voltage on the display should
also change, which indicates the sash position potentiometer is working
correctly.
NOTE:
IN1 SASH POS VER
is a read-only item.
Show Sash % Open
SHOW
SASH%OPEN
The
SHOW SASH%OPEN
item is used to display the current measured
or calculated sash open percentage.
Show Sash Open Area
SHOW SASH AREA
The
SHOW SASH AREA
item is used to display the current measured
or calculated sash open area in ft
2
(or m
2
).
Unit Self Test
SELF TEST
Enter the
SELF TEST
menu item to verify DIM electronics are
functioning correctly. During the self test, the display will show the model
number and software revision of the controller. At the end of the self test,
the display will show
NO ERRORS
if all DIM electronics are good. If unit
displays an
FRAM
error at the end of the test, settings may be
corrupted. Check all menu items to determine cause of
DATA ERROR
.
If unit displays a
CALIB
error at the end of the test, calibration may have
been lost. Verify face velocity, sash sensor and/or flow calibration.
Reset Settings
RESET SETTINGS
The
RESET SETTINGS
item is used to change all settings to factory
default.
RESET SETTINGS
will not affect calibration.
WARNING:
Unconfiguring the unit with the
RESET SETTINGS
item
may change critical settings including control set point.
Always reconfigure unit after using
RESET SETTINGS
item.
Reset Calibration
RESET ALL CALIBS
The
RESET ALL CALIBS
item is used to clear field calibration data.
WARNING:
Clearing field calibration data with the
RESET ALL CALIBS
item may result in incorrect
calibration and/or loss of containment. Always recalibrate
unit after using
RESET ALL CALIBS
item.
Содержание FHC50
Страница 2: ......
Страница 4: ......
Страница 10: ...2 This page intentionally left blank ...
Страница 16: ...Part One 8 This page intentionally left blank ...
Страница 56: ...48 Part Two This page intentionally left blank ...
Страница 96: ...Appendix B 88 This page intentionally left blank ...
Страница 98: ...Appendix C 90 Figure 7 Wiring Diagram Model FHC50 01 Controller ...
Страница 99: ...Wiring Information 91 Figure 8 Wiring Diagram Model FHC50 02 Controller ...
Страница 100: ...Appendix C 92 Figure 9 Wiring Diagram Model FHC50 03 Controller ...
Страница 101: ...Wiring Information 93 Figure 10 Wiring Diagram Model FHC50 04 Controller ...
Страница 102: ...Appendix C 94 Figure 11 Model FHM10 01 Monitor Wiring ...
Страница 103: ...Wiring Information 95 Figure 12 Model FHM10 02 Monitor Wiring ...
Страница 104: ...Appendix C 96 This page intentionally left blank ...
Страница 106: ...Appendix C 98 This page intentionally left blank ...