
Part Two
56
Optimizing Controller Performance
The
Model FHC50
controller uses both integral and PI control methods. Integral control (slower
control signal) is used when the controller is near set point. Integral control provides stability
when natural system fluctuations occur such as operators working at hoods and lab doors
opening. PI control (fast control) is used when responding to large disturbances to face velocity
such as sash movements. PI control rapidly returns the face velocity to set point, thus assuring
containment. Once the
controller is in PI control, it continues to control in this mode until the
operating set point is met.
There are four menu items that change the characteristics of the control output signal;
1) SENSITIVITY
2) SPEED
3) Kc VALUE
4) Ti VALUE
TSI recommends only adjusting the
SENSITIVITY
and
SPEED
to fine tune the control signal.
Only when the
SPEED
and
SENSITIVITY
items cannot provide a stable system should
Kc
VALUE
and
Ti VALUE
be adjusted. The role of each menu item is covered in the
Menu and
Menu Items
section of the manual. This section provides some guidance of when a menu item
should be changed.
The controller is shipped with PI values that are appropriate for 95+ % of the fume hoods
installed. In fume hoods where some adjustment is needed, minor changes to the
SENSITIVITY
and
SPEED
menu items will yield excellent control. The
SENSITIVITY
item selects when the unit
goes into PI control. Each percent of the setting from 100% indicates that the controller must be
1 ft/min away from control set point prior to activating PI control. If the
SENSITIVITY
setting is
60% (40% missing), the face velocity must be 40 ft/min off set point before PI control is activated.
Conversely, if the
SENSITIVITY
setting is 80% (20% missing), the face velocity must only be
20 ft/min off set point before PI control is activated. The default of 80% is usually a good
compromise between PID and integral control.
The
SPEED
menu item slows down the control output. The controller is shipped with a control
signal capable of rotating the damper 90 degrees in 1.5 seconds. This may be too fast if the
damper is in an unstable flow area (very near the exhaust fan), or there are competing air flows in
the laboratory. Controllers modulating a VFD system will probably need to be slowed down, since
the control signal is substantially faster than the VFD/fan can respond.
The remaining menu items,
Kc VALUE
and
Ti VALUE
should not be adjusted unless severe
stability problems exist. Adjusting these variables may improve the response and stability, but the
exact opposite may happen causing the controller to become unstable, hunt substantially, or
have very slow response. If controller performance cannot be improved by adjusting the
SPEED
and
SENSITIVITY
, the two menu items can be manually set to their default values.
Maintenance and Repair Parts
The Model FHC50 Fume Hood Controller requires minimal maintenance. Periodic inspections of
system components as well as an occasional velocity sensor cleaning are all that are needed to
ensure that the Model FHC50 is operating properly. The Model FHC50 should be calibrated
annually. Refer to the
Calibration
section for further information.
Содержание FHC50
Страница 2: ......
Страница 4: ......
Страница 10: ...2 This page intentionally left blank ...
Страница 16: ...Part One 8 This page intentionally left blank ...
Страница 56: ...48 Part Two This page intentionally left blank ...
Страница 96: ...Appendix B 88 This page intentionally left blank ...
Страница 98: ...Appendix C 90 Figure 7 Wiring Diagram Model FHC50 01 Controller ...
Страница 99: ...Wiring Information 91 Figure 8 Wiring Diagram Model FHC50 02 Controller ...
Страница 100: ...Appendix C 92 Figure 9 Wiring Diagram Model FHC50 03 Controller ...
Страница 101: ...Wiring Information 93 Figure 10 Wiring Diagram Model FHC50 04 Controller ...
Страница 102: ...Appendix C 94 Figure 11 Model FHM10 01 Monitor Wiring ...
Страница 103: ...Wiring Information 95 Figure 12 Model FHM10 02 Monitor Wiring ...
Страница 104: ...Appendix C 96 This page intentionally left blank ...
Страница 106: ...Appendix C 98 This page intentionally left blank ...