8-1. Configure TRP-C28
Command
%IDNNPPBBDD(CHK)(cr)
Syntax
Description
%
First leading code
ID
Address of setting module 00-FF(HEX)
NN
New address of setting from 00-FF(HEX)
PP
The Digital I/O module type define to 40
BB
Set new baud rate
(See 8-2)
DD
Data format
(See 8-3)
CHK
Checksum
(cr)
Carriage return
Response
!ID(CHK)(cr)
Command valid
?ID(CHK)(cr)
Command Invalid
8-2 Baud rate setting (BB)
8-3 Data format setting (DD)
Example:
Send command:”%0001400600”…If you turn on the system setting switch, the ID will be reset
to “00”,
New ID is “01”,D I/O type is “40” ,Bard-Rate:9600 ,Checksum setting disable is “00”,
Response:”!01”.
Example:
Send command:%000340054
New ID=“03”,Bard-Rate=“4800”,Checksum=“Enable”,Response:”!03”.
9