Command
ID 05 00 NN DD 00 (CRC)
Syntax
Description
ID
Address of setting module 1~247
05
Function Code
00 NN
NN=00~03 Channel number
DD
Output value DD=00 Relay OFF, DD= FF Relay ON
00
Reserved code
Response
ID 05 00 NN DD 00 (CRC)
Command valid
ID 85 FF (CRC)
Watchdog mode status
ID 85 ER (CRC)
ID 85 :Error Code
ER=00 Syntax error
ER=01 Data Format error
ER=02 Start channel error
ER=03 I/O out of range
*Single-Channel mode (Output control for 1 Bit).
Example:
Send command :” 01 05 00 03 FF 00 ”…...Set up the relay RL4 on.
Response:”01 05 00 03 FF 00 ”….. Command valid.
Send command :” 01 05 00 02 00 00 ”…...Set up the relay RL3 off.
Response:” 01 05 00 02 00 00 ”….. Command valid.
10-16.Set up the digital output status
31