![Truper 100989 Скачать руководство пользователя страница 3](http://html1.mh-extra.com/html/truper/100989/100989_manual_1176353003.webp)
IP Grade
IP20
3
TAMA-2N
100989
3/4”
Class I
60 Hz
Magnetic drill
16 AWG x 2C with an insulation temperature of 221 °F
10 A
1200 W
Code
Description
Weldon socket
Voltage
Frequency
Current
Power
2”
Maximum cutting depth
1 3/8”
Maximum cutting capacity
with annular bits
3/8”
Minimum plate thickness
550 RPM
Speed
50 minutes work x 20 minutes rest-Daily maximum 6 hrs.
Work cycle
Conductors
Insulation
Power Cord Grips used is: Type “Y”.
Tool Build Quality: Basic insulation
Thermal insulation on motor winding: Class E
127 V~
Power requirements
When using an extension cable, verify the gauge is enough for
the power that the tool needs. A lower gauge cable will cause voltage drop in the
line, resulting in power loss and the motor will overheat. The following table shows the right size to use depending on cable’s
length and the ampere capability shown in the tool’s nameplate. When in doubt use the next higher gauge.
When operating power tools outdoors, use a brand grounded extension labeled
“Outdoors Use”. These extensions are specially built for outdoors use and reduce the risk of electric shock.
A
B
To prevent electric shock, the tool shall be grounded while in use.
• Connect the plug into a correctly grounded outlet as shown in example
A
. Not all
the outlets are properly grounded. If in doubt, verify with a qualified electrician.
• If the outlet where you will connect the tool into has two poles (2 orifices),
UNDER ANY CIRCUMSTANCE, DO NOT REMOVE OR ALTER THE PLUG’S GROUND
CONNECTOR. Use a temporary adaptor as shown in example
B
and always connect
the ground conductor lug as shown.
Technical Data
ENGLISH
WARNING
WARNING
Avoid the risk of electric shock or severe injury. When the power cable gets damaged
it should only be replaced by the manufacturer or at a Authorized Service Center.
The build quality of the electric insulation is altered if spills or liquid gets into the tool while in use.
Do not expose to rain, liquids and/or dampness.
Before gaining access to the terminals all power sources should be disconnected.
WARNING
WARNING
WARNING
from 0 A and up to 10 A
from 10 A and up to 13 A
from 13 A and up to 15 A
from 15 A and up to 20 A
18 AWG(*)
16 AWG
14 AWG
8 AWG
16 AWG
14 AWG
12 AWG
6 AWG
3 (one grounded)
from 6’ to 49’ | higher than 49’
Ampere
Capacity
Number of
Conductors
Extension gauge
* It is safe to use only if the extensions have a built-in artifact for over current protection.
AWG = American Wire Gauge. Reference: NMX-J-195-ANCE
CAUTION