background image

20

Advice on water installation

•  You need practical experience to make con-

nections using push-fit systems (e.g. John 
Guest or equivalent).

•  As regards furnace operation, pressure 

pumps and submersible pumps operating 
at pressures as high as 40.6 psi (2.8 bar) as 
well as hot/cold mixing faucets with or with-
out an electrical switch can be installed.

•  If you use a water pump with a pressure 

higher than 40 psi (2.8 bar) or if you connect 
your system to a city water supply, you must 
first install a pressure reducer so that pres-
sure in the water container will not exceed 
40 psi (2.8 bar).

•  The thermal expansion of water during 

heating can result in pressures as high as 
65.25 psi (4.5 bar) before the pressure relief/
drain valve responds. 

•  Water lines connected to the water container 

and the drain valve must withstand tempera-
tures in excess of 176 °F (80 °C). They must 
also be suitable for potable water and must 
withstand pressures as high as 65 psi (4.5 bar).

•  If a submersible pump is used, you must in-

stall a non-return valve (Fig. 26 – 6) between 
the pump and the first branch.

•  If you use pressure pumps that exhibit con-

siderable switching hysteresis, hot water 
can flow back via the cold water faucet. You 
must install a non-return valve (Fig. 26 – 6) 
between the outlet to the cold water faucet 
and the pressure relief/drain valve to prevent 
backflow. Install the water lines so as to en-
sure that all connected components function 
as intended. More specifically, water lines 
must be as short, kink-free, and unstressed 
as possible.

•  Lay cold water lines higher than the pressure 

relief/drain valve. 

Non-compliance will 

void warranty claims for frost damage.

•  There must be a clearance of 1 in. (2.5 cm) 

between water lines and sources of heat.

•  The furnace’s cold water supply must not come 

into contact with cold bridges such as the RV’s 
side wall on account of the risk of frost.

•  An adaptor must be installed at every junc-

tion between a 12 mm push-fit system and 
a 1/2 in. CTS tube; see”Installing a 12 mm / 
1/2 in. CTS adaptor” on page 20.

• 

All hose connections must be secured 
by means of clamps or crimp rings, even 
cold water.

 Installing a 12 mm / 1/2 in. CTS 
adaptor

An adaptor must be installed at every junction 
between a 12 mm push-fit system and a 1/2 in. 
CTS tube; see Fig. 28 – 1.

12 mm 
Adaptor

1/2 in. CTS tube

2

1

3

1 in. (25 mm)

Fig. 28

1  Adaptor 12 mm to 1/2 in. CTS tube
2  1/2 in. CTS tube
3  Clamp or crimp ring 

(not included in scope of delivery)

Содержание Combi comfort

Страница 1: ...nly for use by trained and qualified technicians To the installer The operating instructions for this Truma furnace are part of these installation instructions The operating instructions are included...

Страница 2: ...3 Installing the CP plus control panel 23 Installing the room temperature sensor 23 Electrical connections 24 Setting up a 12 volt connection 25 Connecting the room temperature sensor 25 Connecting th...

Страница 3: ...r optional H Warm air ducts with insulation sleeve Mounting arrangement Accessories This is a typical installation for illustration The installation in your vehicle may vary The illustration is not to...

Страница 4: ...4 1 top 7 6 9 9 10 19 7 6 4 11 3 2 5 18 8 Furnace diagram Fig 3 Fig 2 13 11 17 16 14 15 12 3 2 5 6 7 4 1 top 9 18 10 10 19 20b 20a 8...

Страница 5: ...ole 120 volt electrical plug NEMA 5 20P only on Combi eco plus and Combi comfort plus models 9 Plastic frame feet 10 Aluminum frame feet 11 Circulated air fan 12 Fan for combustion air 13 Cold water c...

Страница 6: ...when connecting the Combi furnace Close the vehicle s gas supply during in stallation and when connecting the Combi furnace Always wear protective gloves to avoid inju ries from sharp edges during in...

Страница 7: ...loors typically used in RVs can change color due to the temperature of the Combi furnace Truma does not accept liability for this Truma recommends removing the PVC in the area of the furnace Damage to...

Страница 8: ...e quires room air The opening for the circulated air intake RV s interior installation space must be at least 23 in 150 cm free cross section Service technicians must be able to readily access as well...

Страница 9: ...An improperly secured Combi furnace can be come dislodged in an RV accident and the gas line can become disconnected The floor or false floor must bear the load of a secured furnace Contact the Truma...

Страница 10: ...riginal exhaust accessories listed here 4 1 2 6a 6b 6 8 7 5 7 Side wall Outside RV Inside RV 3 5 x 25 8x 3 1 2 4 Combi Wall cowl 3 9 10 Fig 6 Item Quant Exhaust accessories Exhaust venting system 1 1...

Страница 11: ...ated above or at the same level If any portion of the wall cowl is below the spout then the clearance must amount to the sum of the vertical distance below the spout plus 3 ft 0 9 m Description USA Ca...

Страница 12: ...tube and the combustion air supply tube to length 2 Squeeze each end of the exhaust tube Fig 10 1 inward shortening it by approx 1 in 2 cm at each end 3 Slide the combustion air supply tube over the...

Страница 13: ...supplied screws are too short be cause of the non smooth surface structure use equivalent tapping screws that are long enough and that are made of stainless steel HOT Fig 13 Installing the inner part...

Страница 14: ...The furnace draws in circulated air from inside the vehicle Risk of carbon monoxide poisoning If exhaust enters the RV carbon monoxide in the exhaust can poison people and cause death The opening for...

Страница 15: ...m one of the two lower warm air outlets Fig 17 L may be closed with a VD Combi blank cover We recommend equipping all 4 warm air outlets with warm air ducts for ideal distri bution of warm air in the...

Страница 16: ...above the floor not exceeding the height of the warm air outlet the duct is attached to for ducts with a length of more than 5 ft 1 5 m in front of the first outlet 4 in 100 mm above the floor for duc...

Страница 17: ...tlet to tighten the LT T pipe Segmented threads allow you to push the end outlet against the wall before tighten ing it by turning The insertion position is marked by notches on both parts 3 Insert th...

Страница 18: ...g 24 Damage to the flare fitting The flare fitting is a dry seal Never use pipe dope on the flare fitting 2 Screw the gas line s union nut wrench size 3 4 in 19 mm onto the Combi furnace s gas connect...

Страница 19: ...1 14 9 4 2 Fig 26 1 Adaptor 12 mm to 1 2 in CTS tube 2 1 2 in PEX x 1 2 in NPT female threaded adapter 3 1 2 in CTS PEX tube 4 T piece 1 2 in CTS PEX tube not included 5 Truma water pressure regulator...

Страница 20: ...siderable switching hysteresis hot water can flow back via the cold water faucet You must install a non return valve Fig 26 6 between the outlet to the cold water faucet and the pressure relief drain...

Страница 21: ...ter line Insert the water pressure regulator in the proper direction Direction of flow is indi cated by arrow Screw the connecting parts not in scope of delivery with a nominal torque of 2 2 lb ft 3 N...

Страница 22: ...readed adapter 7 1 2 in CTS PEX tube 8 Cold water line inlet 1 2 in CTS PEX tube 9 1 2 in x 1 2 in x 1 2 in PEX tee 10 Cold water line outlet 1 2 in CTS PEX tube 11 Crimp ring or clamp 1 Drill a hole...

Страница 23: ...tasks Pull on all the water connections to ensure that they are securely connected Check all water connections for leaks Repair leaks as needed Repeat check for leaks and take any neces sary steps to...

Страница 24: ...electrical compo nents to the connector cables Connector cables and lines must be se curely fastened they must not become loose or be disconnected due to vibration Electric lines switching equipment...

Страница 25: ...onnectors 0 25 in x 0 032 in 6 3 x 0 8 mm TE PIDG FASTON 250 series DO NOT connect any other load to the 12 V connection Connecting the room temperature sensor Insert the connector cable into the conn...

Страница 26: ...ons Test water connections water lines and joints for leakage Be absolutely certain that all water drains properly No warranty claims will be ac cepted for frost damage 2 Hand over the operating instr...

Страница 27: ...ssure test The Combi furnace has an automatic fan speed control Truma recommends that all 4 warm air outlets should be fitted with warm air ducts 1 For testing close all warm air outlets but one The s...

Страница 28: ...Control Heating Unit Option Control_PCB Flame detection Igniter CATS Circulation Air FAN WTSS WTS ATSS ATS Combustion Air FAN Blue Blue Blue Blue _ _ Blue Gray Gray Gray White White Black Red Red Red...

Страница 29: ...E_PCB AECO E Manual Reset Electric Heating Rod 120V AC Plug Control_PCB GND GND N VCC K 3 K 2 K 1 GND 120 ON L R1_N R2_N R1_L R2_L Green White Black NEMA 5 20P If any of the original wire as supplied...

Страница 30: ...ers Chlorine based swimming pool chemicals Water softening chemicals De icing salts or chemicals Carbon tetrachloride Halogen type refrigerants Cleaning solvents such as perchloroethylene Printing ink...

Страница 31: ...3 15 in 80 mm Clamp for holding the warm air duct AD 65 with insula tion sleeve 40171 11 40171 61 bulk 200 pieces End outlet EN brown Closable warm air outlet Air throttle can be rotated 360 to direct...

Страница 32: ...40701 52 bulk 100 pieces Wall outlet vent WL To release a small flow of warm air along the wall 40191 02 40191 52 bulk 55 pieces Y piece To branch off another warm air duct AD 65 40161 02 40161 52 bu...

Страница 33: ...r end outlet nut EM T piece TS T pipe LT and Combi for secure fastening of air duct AD 65 34310 02 34310 52 bulk 200 pieces Blank cover VD Combi To close one of the lower warm air outlets of the Combi...

Страница 34: ...34 17 18 22 19 15 16 10 11 1 12 5 6 7 13 14 x 20 x x 22 2 3 4 23 24 12 V 21 25 26 x Appendix C Exploded view of spare parts and accessories...

Страница 35: ...emperature sensor 16 34000 71900 Cable for room sensor 13 1 ft 4 m 17 34020 00178 Elbow tting with aeration valve for rigid piping 12 mm 18 34000 17700 Condensation tube 3 ft 0 9 m long 19 34020 00177...

Страница 36: ...Please have the model number and serial number on furnace s type plate handy when you call Manufacturing Truma Ger tetechnik GmbH Co KG Wernher von Braun Stra e 12 85640 Putzbrunn Germany www truma co...

Отзывы: