Electronic Temperature Control (cont.)
L A E C O N T R O L L E G E N D
Info/Set Point
Manual Activation/
Up Arrow
Manual Defrost/
Down Arrow
Stand-By/
Cancel
Compressor Running
Activation of 2
nd
Parameter Set
Alarm
Cabinet in Defrost
Evaporator Fan Running
Step 3: Change High Alarm Setting (AhA)
1.
While the display shows
AhA
, press and hold info
to
show the current setting.
DO NOT RELEASE THE BUTTON!
.
2.
While holding info, press the up
or down
arrows
to change the current setting.
RECOMMENDED:
Be sure the high alarm setting
is at
least 1° warmer
than the Cut-In temperature to prevent a
false alarm.
3.
Release all buttons. Proceed to step 4.
Step 4: Change Alarm Delay (Atd)
1.
Press info
until the display shows
Atd
.
2.
While the display shows
Atd
, press and hold info to show
the current setting.
DO NOT RELEASE THE BUTTON!
3.
While holding info, press the up
or down
arrows
to change the current setting.
NOTE:
Alarm delay is measured in minutes.
RECOMMENDED:
Be sure the time delay is at least 5 min
to prevent a false alarm.
4.
Release all buttons and wait for the control to display the
current cabinet temperature.
Содержание TSCI Series
Страница 2: ...truemfg com TEC_TM_098 REV A 10 12 2020 Page 2 of 32 S C I E N T I F I C S E R I E S Notes ...
Страница 28: ...truemfg com TEC_TM_098 REV A 10 12 2020 Page 28 of 32 S C I E N T I F I C S E R I E S Notes ...
Страница 29: ...TEC_TM_098 REV A 10 12 2020 Page 29 of 32 truemfg com S C I E N T I F I C S E R I E S Notes ...
Страница 30: ...truemfg com TEC_TM_098 REV A 10 12 2020 Page 30 of 32 S C I E N T I F I C S E R I E S Notes ...
Страница 32: ...TEC_TM_098 REV A 10 12 2020 Page 32 of 32 www truemfg com EA BP_MISC_2268_10 2020 ...