TAC-27K / TAC-27K-HC-LD: AIR CURTAIN
www
.
truemfg
.
com
THE SET POINT IS WHERE THE COMPRESSOR WILL
SHUT OFF.
HOW TO SEE AND MODIFY THE SET POINT:
STEP 1
- Model XW60VS push and immediately release
the (SET) key. Model XR160C push and hold the (SET)
key: The display will show the (SET) point value.
STEP 2
- The (SET LED) will start blinking.
STEP 3
- To change the (SET) value, push the (UP) or
(DOWN) arrows within (10) seconds.
STEP 4
- To memorize the new set point value, push
the (SET) key again or wait (10) seconds.
THE LOCAL DISPLAY SHOWS WHICH
PROBE IS READING.
HOW TO SEE “LOD” LOCAL DISPLAY:
STEP 1
- Press and hold the (SET) and (DOWN)
arrows at the same time for (7-12) seconds.
STEP 2
- You should then see (HY).
STEP 3
- Release the keys.
STEP 4
- Press the down arrow until you see the
letters (LOD).
STEP 5
- Press the (SET) button. You should see P1,
P2, P3. This is the probe used for the display. (All probes
may not be used in some applications). To change, press
the (UP / DOWN) arrow to set a new number and then
push the (SET) button to save these changes.
Wait 10 seconds for control to display temperature.