Fig. 57: Outdoor air filter
3.
Open the quick release fasteners ( Fig. 57 /1) and
pull the outdoor air filter ( Fig. 57 /2) out of the
filter chamber by the frame.
①
②
Fig. 58: Extract air filter
4.
Pull the extract air filter ( Fig. 58 /1) out of the filter
chamber ( Fig. 58 /2).
5.
Check both filters for damage, contamination and
deposits.
6.
Remove contamination in the ventilation unit with
a commercially available vacuum cleaner.
7.
If a filter is intact, free of contamination and
deposits, and if it has been used for less than
1 year, put it back into the filter chamber.
If a filter has already been used for a year or if
it does no longer meet the technical or hygiene
requirements, replace it.
When you insert a new filter, make sure that
the labelling at the front of the filter remains
visible.
Observe the direction of the arrow for the
extract air filter.
Once installed, each filter must be flush with
the surface as otherwise air will bypass the
filter.
8.
Close and lock the inspection access doors.
9.
Switch on the power supply.
10.
If the filter operating hours counter in FSL
‑
CON-
TROL III has been used, reset it after a filter
change
Ä
Installation and configuration manual
FSL
‑
CONTROL III.
ð
Filter checking or filter change is complete.
Dispose of used filters with residual waste.
Maintenance
Maintenance > Checking and replacing the filters
Decentralised ventilation units SCHOOLAIR-S-HV
42
Содержание SCHOOLAIR-S-HV
Страница 40: ...Operation Control panel Analogue control panel settings Decentralised ventilation units SCHOOLAIR S HV 40...
Страница 48: ...Appendix Appendix Decentralised ventilation units SCHOOLAIR S HV 48...
Страница 54: ...Decentralised ventilation units SCHOOLAIR S HV 54...
Страница 55: ...Decentralised ventilation units SCHOOLAIR S HV 55...