3.2 ATEX areas of application
ATEX areas of use, depending on the type of release mechanism, actuation, ambient temperature and air-
flow velocity
Release
mechanism
Type of actuation
Labelling
Ambient
temperature
Maximum air
velocity
ExPro-TT
ExMax-15-BF-TR
II 2G Ex h IIC T6 Gb
II 2D Ex h IIIC T80°C Db
-40 °C ≤ Ta ≤ +40 °C 10 m/s
ExPro-TT
ExMax-15-BF-TR
II 2G Ex h IIC T5 Gb
II 2D Ex h IIIC T95°C Db
-40 °C ≤ Ta ≤ +50 °C 10 m/s
ExPro-TT
RedMax-15-BF-TR
II 3G Ex h IIC T6 Gc
II 3D Ex h IIIC T80°C Dc
-40 °C ≤ Ta ≤ +40 °C 10 m/s
ExPro-TT
RedMax-15-BF-TR
II 3G Ex h IIC T5 Gc
II 3D Ex h IIIC T95°C Dc
-40 °C ≤ Ta ≤ +50 °C 10 m/s
Technical data
ATEX areas of application
Explosion-proof fire damper Type FKRS-EU
7
Содержание FKRS-EU Series
Страница 12: ...Explosion proof fire damper Type FKRS EU 12...