6
EM-TRF · EM-TRF-USV Operating and Installation Manual / Leaflet no. M375EV5 (
8/2018
)
3 Product description
EM-TRF · EM-TRF-USV
Supply voltage
230 V AC ±10 %, 50-60 Hz
Power consumption
up to 40 VA for a controller with all expansion modules
up to 35 VA for a fume cupboard controller with control panel
up to 33 VA for a room controller with room control panel
up to 29 VA for a room controller without room control panel
up to 9 VA for an EASYLAB TAM adapter module
Primary fuse
500 mA, slow blow, 250 V
Terminal block
Cable cross-section up to 2.5 mm²
Acceptable temperature range
for storage −10 to +70 °C
for operation 0 to +50 °C
Protection level
IP 20
Dimensions
B × H × T: 78 × 65 × 100 mm
Weight
1,3 kg
Technical data
Additional data for the EM-TRF-USV
USP operation
One controller (TCU3 or TAM) with a
control panel
Approx. 4.5 h for maintaining normal operation
Approx. 6 h for a defined blade position and indication of mains voltage
interruption
Shelf life
6 months from delivery to commissioning
Service life
Up to 4 years
Weight
2,4 kg (incl. Battery pack 1,1 kg)