Trox Technik EM-TRF Скачать руководство пользователя страница 4

General information regarding safety

Only skilled qualified personnel are allowed to 

perform the described work on the expansion 

modules. 

Only skilled qualified electricians are allowed to

work on the electrical system.
For all work performed on the EASYLAB 

components, the following regulations and 

guidelines must be complied with. This applies in

particular to the following German country specific

regulations or as appropriate in the country where

the installation is taking place:
• Equipment and Product Safety Laws (GPSG)
• Industrial Health and Safety Regulations

(BetrSichV)

• Accident Prevention Regulations 

(BGV A1, BGV A3)

General safety measures

• Large temperature differences

Condensation can damage the electronics 

beyond repair. If the expansion module has been

kept in an unheated area, wait at least two hours

before switching on the supply voltage for 

commissioning.

• Electrostatic charge

Electrostatic charge can damage the electronics.

To avoid this, first touch an equipotentially 

bonded metal surface, e.g. 

a water pipe, for electrical earthing before you

remove the expansion module from its protective

wrapping. Avoid skin contact with any 

components or printed circuits on the expansion

module or the main PCB.

• Weight

The expansion PCB is equipped with a 

transformer that has a comparatively high 

weight. To avoid injury and damage, be sure to

grip the PCB properly and to handle it with care.

• Installing the PCB

Tighten the mounting screws only hand-tight to

avoid damage to the PCB or to the fixing points 

in the casing.

• Foreign matter and liquids

If liquid gets onto the PCB or inside the expansion

module, let the expansion module completely dry

before commissioning. Remove foreign matter, if

any.
If the device emits a smell or smoke, have it 

checked by the manufacturer.

4

EM-TRF · EM-TRF-USV Operating and Installation Manual / Leaflet no. M375EV5 (

8/2018

)

2 Safety and correct use

Correct use

The EM-TRF and EM-TRF-USV expansion modules

are used to connect TCU 3 EASYLAB controllers

and TAM adapter modules to a 230 V AC supply

voltage. 
• Use the expansion module only with a TCU3

EASYLAB controller or a TAM adapter module.

• Do not connect EASYLAB controllers with an 

EM-TRF or EM-TRF-USV expansion module to 

a 24 V power supply.

• Only connect the expansion module to the 

dedicated socket on the main PCB of the 

TCU3 or TAM.

• Observe the technical data of the expansion

module.

Incorrect use

Do not use the expansion module outdoors, in wet

areas, or in potentially explosive atmospheres.

Residual risks

Uninterruptible power supply is provided only 

with the EM-TRF-USV being connected to a fully

charged battery pack. For maximum operating

times with uninterrupted power supply refer to 

the technical data.

Содержание EM-TRF

Страница 1: ...flet no M375EV5 8 2018 The art of handling air The art of handling air Operating and Installation Manual EASYLAB Expansion modules Type EM TRF for 230 V AC mains voltage Type EM TRF USV for 230 V AC m...

Страница 2: ...Technical data ______________________ 6 4 Transport storage and packaging ________ 7 5 Installation __________________________ 8 Installing the EM TRF and EM TRF USV __ 8 Fitting the safety latch ____...

Страница 3: ...sential to read this operating and installation manual before starting any work and to comply with it The manual must be given to the facilities manager when handing over the system The facilities man...

Страница 4: ...ped with a transformer that has a comparatively high weight To avoid injury and damage be sure to grip the PCB properly and to handle it with care Installing the PCB Tighten the mounting screws only h...

Страница 5: ...ansformer reduces this voltage to 24 V AC to be supplied to the controller and its modules An LED indicates whether voltage is being supplied Additional function of the EM TRF USV If the supply voltag...

Страница 6: ...for an EASYLAB TAM adapter module Primary fuse 500 mA slow blow 250 V Terminal block Cable cross section up to 2 5 mm Acceptable temperature range for storage 10 to 70 C for operation 0 to 50 C Prote...

Страница 7: ...xpansion module Battery pack with connecting cable and plug Fixing bracket Fixing screws Transport on site If possible take the expansion module in the transport packaging up to the installation locat...

Страница 8: ...o avoid injury and damage be sure to grip the PCB properly and to handle it with care Installing the EM TRF and EM TRF USV Step 1 1 Interrupt the voltage supply to the TCU3 controller or TAM adapter m...

Страница 9: ...a 230 V power supply is connected 1 Place the supplied safety latch on the casing 2 Drill a hole into the casing 3mm 3 Fix the latch with the supplied screw to the lid of the casing The casing can now...

Страница 10: ...If necessary the bracket can be bent for fixing it to the control unit 5 Installation Installation examples Battery pack Screw Bracket VAV terminal unit Important Be careful when fixing the brackets...

Страница 11: ...the EM TRF and EM TRF USV Never connect two voltages When the expansion module for 230 V AC is used do not connect a 24 V AC DC voltage to the main PCB Connect the 230 V AC supply voltage to the upper...

Страница 12: ...onfiguration software provides a commissioning wizard that guides users in making project specific adjustments Maintain standard operation i e control function factory setting Close the control damper...