Changes to the speed to adjust process variables
(controlled operation) should be max. 16.7 rev/sec
(1.75 rad/sec), except when running through reso-
nance frequencies.
The fans’ service life can be increased by quickly
running through resonance frequencies.
The operating manuals from the control unit manu-
facturer must be observed.
The EMC Directive 2014/30/EU must be complied
with.
General notes
The motor and transformer must be positioned as
close to one another as possible
Cables must be sheathed and shielded
Cables, cable ends, the frequency inverter and the
motor must be earthed.
It is advisable to use all-pole sine filters.
3.6.3 Smoke extract
During smoke extract operation, the fans only extract
smoke gases in the event of a fire to remove the smoke
from the fire compartments.
CE marking of smoke exhaust fans (BV)
Fig. 12: CE marking
The rating plate of the smoke exhaust fans (BV) also
contains information about the application and permis-
sible temperature / time category.
In addition, a CE mark as per EN 12103, Part 3, is
attached to demonstrate product conformity.
3.7 Rating plate
Fig. 13: Fan’s rating plate
The fan’s rating plate (Fig. 13, Fig. 14/1) is located on
the outside and contains the following information,
among other things:
Manufacturer
Year of manufacture
Manufacturing no.
Part no.
Type
Volume flow rate
Speed
Motor rating
Total pressure increase
Voltage (V) / frequency (Hz)
Fig. 14: Arrangement of the rating plates on axial fans
Technical data
Rating plate
Axial fans AXO/BVAXO; AXN/BVAXN; ZAXN/BVZAXN
20