Operating manual – Dehumidifier TTR 200/300
EN(UK)
B-5
11. Transport and storage
Transport
Caution!
Damage to device due to vibrations.
Strong vibrations can cause damage to the device.
When transporting the device, protect it from exces-
sive shocks, e.g. by rough handling or dropping.
During transport, always secure the device against
slipping.
Lift and carry the device only by using the provided
means.
Storage
Store the device in a dry place where it is protected from adverse weather
effects.
Choose a storage location that is free of dust.
Always disconnect the device from the mains supply when it is not in use.
Up to 4 devices can be stacked in a space-saving way.
Always secure stacked devices against tipping.
12. Care and maintenance
Care
The housing surface of the device comes with a low-maintenance pow-
der coating. This decreases the adhesion of dirt and enables cleaning
with a damp piece of cloth.
Cleaning of the interior and the integrated components may only be car-
ried out by trained personnel or the Trotec customer service.
Caution!
Damage to the device due to improper cleaning.
The interior of the device must only be cleaned with
a damp cloth or pressurised air. Do not let any liquids
enter the device!
Maintenance
Trotec dehumidifiers are designed for long operating hours with low
maintenance requirements. To ensure safe operation of the device, all in-
tegrated components must be checked and cleaned or replaced
at least
once every 6 months or 4,000 operating hours
if necessary.
Caution!
Damage to the device due to improper handling.
Cleaning, maintenance and repair of electric and
mechanical components may only be carried out by
trained personnel or the Trotec customer service.
Replacing the filter
The intervals for replacing the filter depend on air contamination and filter
quality. Contaminated filters affect the efficiency of the humidifier. For this
reason, filters should be checked and cleaned or replaced
once every
week (daily on construction sites)
if necessary.
Danger!
Risk of injury at the fan.
Before removing the air lter, the device must be
switched off and secured against accidental activa-
tion, particularly if the fan inlet is freely accessible!
1
2
Fig.: Air filter replacement TTR 200/300
1 Filter cover
2 Filter mat
10. Troubleshooting
Error
Diagnosis
Possible cause
Remedy
No dehumidification
Drying air does not show any
temperature increase
Rotor drive defective
Check the rotor drive and repair if
necessary
Ampere meter displays consider-
ably deviating values
Heating unit defective
Replace heating unit
Ampere meter displays deviating
values
Insufficient regeneration air flow
Check free air flow,
check flan,
clean or replace the air filter