7
EN
User instructions – Adsorption dehumidifier TTR 160/250
Replacing the filter
The intervals for replacing the filter depend on air contamination and
filter quality. Contaminated filters affect the efficiency of the dehumidifier.
For this reason, filters should be checked and cleaned or replaced
once
every week (daily on construction sites)
if necessary.
Danger!
Risk of injury at the fan.
Before removing the air filter, the device must be
switched off and secured against accidental activa-
tion, particularly if the fan inlet is freely accessible!
1
2
Fig.: Air filter replacement TTR 400D/500D
1 Filter cover
2 Filter mats
To remove the filter mat (2), loosen the screws at the cover (1) and care-
fully lift the cover. Ensure that the protective conductor, which is con-
nected to the cover, is not damaged.
By default, all devices are equipped with a reusable filter mat (PPI30).
This mat can be cleaned by beating or washing it.
Caution!
Damage to the device due to liquids.
Before inserting the air filter, always ensure that it
has dried completely. Otherwise, there is the risk
that the fan takes in liquids and is damaged due to
a short circuit.
12. Dangerous substances
When operating the dehumidifier in rooms that are contaminated by cer-
tain chemical substances, the dehumidification unit (rotor) may be dam-
aged permanently. The substances remain in the rotor and may deterio-
rate the performance of the device by clogging the silica gel pores or lead
to chemical reactions of the gel.
This permanently affects the performance and service life of the
dehumidifier.
For this reason, it must be ensured, that the applied dehumidification
agent, i.e. the silica gel, cannot come into contact with dangerous sub-
stances. The following list includes substances with a proven deteriorat-
ing effect on the dehumidification rotors (silica gel) used in this device.
Even small quantities of these or similar substances must be prevented
from coming into contact with the device.
Inorganic substances
Lithium chloride
LiCl
Deterioration of the performance
Sodium hydroxide
NaOH
Destruction of the silica gel structure
Potassium hydroxide
KOH
Destruction of the silica gel structure
Sodium chloride
NaCl
Deterioration of the performance
Potassium chloride
KCl
Deterioration of the performance
Calcium chloride
CaCl2
Deterioration of the performance
Magnesium chloride
MgCl2
Deterioration of the performance
Ammonia
NH3
Deterioration of the performance
Hydrofluoric acid
HF
Destruction of the mech. stability
Aluminium chloride
AlCl3
Deterioration of the performance
Sea water
Deterioration of the performance
Steam with high temp.
Destruction of the silica gel structure
Softener
Clogging of silica gel pores
Strong acids
pH ≤ 2…3 Destruction of the mech. stability
Bases
pH ≥ 7…8 Destruction of the sorption capacity of
the silica gel
Amines
R-NH2
Deterioration of the performance
Organic substances
Oil mist
Clogging of silica gel pores
Cyclohexanone
C6H10
Deterioration of the performance
Isopropyl alcohol
(CH8)2CHOH
Deterioration of the performance
o-Xylene
C6H4(CH2)2
Deterioration of the performance
m-Xylene
C6H4(CH2)2
Deterioration of the performance
p-Xylene
C6H4(CH2)2
Deterioration of the performance
Phenol
C6H5OH
Deterioration of the performance
o-Dichlorobenzene
C6H4CL2
Deterioration of the performance
Methyl bromide
CH3Br
Deterioration of the performance
Glycerine
C3H8O3
Deterioration of the performance
Additionally, the air that is taken in by the device must not contain any
substances with melting points below 200 °C!
Immediately before commissioning the dehumidifier, the following re-
quirements must be fulfilled:
•
The dehumidifier may only be used according to the parameters
specified in chapter "Technical data".