background image

 

7

EN

User instructions – Adsorption dehumidifier TTR 160/250

Replacing the filter

The intervals for replacing the filter depend on air contamination and 
filter quality. Contaminated filters affect the efficiency of the dehumidifier. 
For this reason, filters should be checked and cleaned or replaced 

once 

every week (daily on construction sites)

 if necessary.

Danger! 

Risk of injury at the fan.

Before removing the air filter, the device must be 
switched off and secured against accidental activa-
tion, particularly if the fan inlet is freely accessible!

1

2

Fig.: Air filter replacement TTR 400D/500D

1 Filter cover
2 Filter mats

To remove the filter mat (2), loosen the screws at the cover (1) and care-
fully lift the cover. Ensure that the protective conductor, which is con-
nected to the cover, is not damaged.

By default, all devices are equipped with a reusable filter mat (PPI30). 
This mat can be cleaned by beating or washing it.

Caution! 

Damage to the device due to liquids.

Before inserting the air filter, always ensure that it 
has dried completely. Otherwise, there is the risk 
that the fan takes in liquids and is damaged due to 
a short circuit.

12. Dangerous substances

When operating the dehumidifier in rooms that are contaminated by cer-
tain chemical substances, the dehumidification unit (rotor) may be dam-
aged permanently. The substances remain in the rotor and may deterio-
rate the performance of the device by clogging the silica gel pores or lead 
to chemical reactions of the gel.

This permanently affects the performance and service life of the 
dehumidifier.

For this reason, it must be ensured, that the applied dehumidification 
agent, i.e. the silica gel, cannot come into contact with dangerous sub-
stances. The following list includes substances with a proven deteriorat-
ing effect on the dehumidification rotors (silica gel) used in this device. 
Even small quantities of these or similar substances must be prevented 
from coming into contact with the device. 

Inorganic substances 

Lithium chloride  

LiCl

Deterioration of the performance 

Sodium hydroxide

NaOH

Destruction of the silica gel structure

Potassium hydroxide

KOH

Destruction of the silica gel structure

Sodium chloride

NaCl

Deterioration of the performance

Potassium chloride

KCl

Deterioration of the performance

Calcium chloride

CaCl2

Deterioration of the performance

Magnesium chloride

MgCl2

Deterioration of the performance

Ammonia

NH3

Deterioration of the performance

Hydrofluoric acid

HF

Destruction of the mech. stability

Aluminium chloride

AlCl3

Deterioration of the performance

Sea water

Deterioration of the performance

Steam with high temp.

Destruction of the silica gel structure

Softener

Clogging of silica gel pores

Strong acids

pH ≤ 2…3 Destruction of the mech. stability

Bases

pH ≥ 7…8 Destruction of the sorption capacity of 

the silica gel

Amines

R-NH2

Deterioration of the performance

Organic substances 

Oil mist

Clogging of silica gel pores

Cyclohexanone

C6H10

Deterioration of the performance

Isopropyl alcohol

(CH8)2CHOH

Deterioration of the performance

o-Xylene

C6H4(CH2)2

Deterioration of the performance

m-Xylene

C6H4(CH2)2

Deterioration of the performance

p-Xylene

C6H4(CH2)2

Deterioration of the performance

Phenol

C6H5OH

Deterioration of the performance

o-Dichlorobenzene

C6H4CL2

Deterioration of the performance

Methyl bromide

CH3Br

Deterioration of the performance

Glycerine

C3H8O3

Deterioration of the performance

Additionally, the air that is taken in by the device must not contain any 
substances with melting points below 200 °C!

Immediately before commissioning the dehumidifier, the following re-
quirements must be fulfilled: 

 The dehumidifier may only be used according to the parameters
specified in chapter "Technical data".

Содержание TTR 160

Страница 1: ...User instructions Adsorption DehumidiFier TTR 160 TTR 250 EN EN...

Страница 2: ...efer to the General Terms and Conditions GTC available on our website www trotec de 1 Notes on how to use the manual Translation of the original instructions 2006 42 EC This operating manual contains...

Страница 3: ...annot be achieved with condensation dehumidifiers for physi cal reasons Additionally adsorption dehumidifiers are considerably more economic at these operating temperatures 4 General safety instructio...

Страница 4: ...via the sections so that it can permanently absorb and release humidity Process air Air to be dehumidified is taken in by means of a fan and divided into two air streams Process air 4 and regeneration...

Страница 5: ...ed To prevent an air short circuit with the humid exhaust air the humid air outlet of free intake devices is to be laid away at a minimum distance of approx 1 0 m from the device Presettings Ventilati...

Страница 6: ...ill light up Switching the device off The device can be switched off at the power switch 6 The integrated control indicator will go out Remote operation The device can be switched on at the power swit...

Страница 7: ...deteriorat ing effect on the dehumidification rotors silica gel used in this device Even small quantities of these or similar substances must be prevented from coming into contact with the device Inor...

Страница 8: ...be disposed of in the designated containers according to local regulations or at a recycling depot 14 Service and repair Danger Danger to life due to improper repair Never attempt to carry out modifi...

Страница 9: ...110 000 130 EAN number 4 052 138 000 784 4 052 138 002 445 Dehumidification performance 0 5 kg h 1 1 kg h Range of application for drying air 60 160 m h 130 300 m h Nominal air volume pressing 155 m...

Страница 10: ...XS1 1 2 3 PE PE sw schwarz black rt rot red ge gelb yellow bl blau blue br braun brown K1 A1 A2 air dehumidifier TTR 160 no rev Titel E EA 160 0001 01 Trotec GmbH Grebbenerstr 7 52525 Heinsberg trans...

Страница 11: ...XS1 1 2 3 PE PE sw schwarz black rt rot red ge gelb yellow bl blau blue br braun brown K1 A1 A2 air dehumidifier TTR 250 no rev Titel E EA 250 0002 01 Trotec GmbH Grebbenerstr 7 52525 Heinsberg trans...

Страница 12: ...Dimensions TTR 160 40 199 50 60 DN63 98 DN100 38 306 306 82 213 28 244 40 50 61 24 304 40 Dimensions TTR 250 282 79 DN80 98 DN100 339 115 75 241 354 273 212 78 24...

Страница 13: ...ective cover P 1000 1053 12 Ampere meter P 1000 1058 13 Operating hour counter P 1000 1137 14 Cable bushing P 1000 0973 15 Filter mat P 1000 1192 Item Designation Article number 16 Gear motor P 1000 1...

Страница 14: ...ective cover P 1000 1053 12 Ampere meter P 1000 0179 13 Operating hour counter P 1000 1137 14 Cable bushing P 1000 0937 Item Designation Article number 15 Filter mat P 1000 1194 16 Gear motor P 1000 1...

Страница 15: ...exigences fondamentales de s curit et de sant Cette d claration n est valable que dans la version que nous avons mise en circulation Funktion Adsorptions Luftentfeuchter Function Adsorption Air Dehum...

Страница 16: ...trotec GmbH Grebbener str 7 D 52525 Heinsberg 49 2452 962 400 49 2452 962 200 info trotec com www trotec com...

Отзывы: