Trotec TTK 1500 Скачать руководство пользователя страница 14

12

Operating Manual – Dehumidifier TTK 1500

EN

Activities for before the start of maintenance

1. Do not touch the mains plug with wet or damp hands.

2. Before any work, detach the mains plug!

Maintenance tasks at the electrical equipment or
the air-conditioning technology must only be
carried out by specialist companies for cooling and
air-conditioning or by Trotec.

Visual check for dirt in the inside of the device

1. Remove the air filter (see chapter "Cleaning the air inlets and

the air filter").

2. Shine a torch through the opening of the device.

3. Check the inside of the device for dirt.

4. If you find dirt, use a high pressure cleaner to clean the device

according to "Cleaning the air inlets and the air filter".

5. Put the air filter back in.

Cleaning the air inlets and the air filter

A.

50 cm

B.

C.

90°

50 cm

Содержание TTK 1500

Страница 1: ...TTK 1500 OPERATING MANUAL DEHUMIDIFIER EN TRT BA TTK1500 TC 001 EN...

Страница 2: ......

Страница 3: ...tronically processing duplicating or spreading the publication Subject to technical changes All rights reserved Trademarks are used without guarantee that they may be used freely and primarily followi...

Страница 4: ...e and the relative humidity the condensed water either drops continuously or only during the defrost phase into the condensation tray The condensation is fed through a pressure resistant pipe connecti...

Страница 5: ...ues Model TTK 1500 Dehumidifying capacity max 400 l 24 h Dehumidifying capacity 20 C 60 relative humidity 100 l 24 h Suitable for room dimensions up to construction drying or clearing water damages ma...

Страница 6: ...WITCH CYCLE FAULT LAMP FAN MOTOR FAN CAP DELAY TIMER CONTACTOR COMPRESSOR CONDENSATE PUMP PUMP FUSE HUMIDISTAT FLOAT SWITCH RELAY No 1 ISOLATOR RELAY No 2 HIGH LEVEL PUMP RUN FLOAT SWITCH L1 L3 L2 HOU...

Страница 7: ...ying and dehumidifying room air while adhering to and following the technical data Intended use encapsulates drying and dehumidifying production plants underground rooms store rooms archives laborator...

Страница 8: ...ift or an elevating truck Before transporting the device proceed as follows 1 Switch off the device at the mains switch see chapter Operating elements 2 Remove the mains plug from the mains socket Do...

Страница 9: ...sing a generator ensure that the generator supplies at least 4 kW of power device starting current can exceed the nominal current by four or five times Also note this fact when using several devices a...

Страница 10: ...ain hose is properly connected to the device and is free of damage 2 Depending on use position the end of the condensation drain hose as follows Position a sufficiently large container at least 90 lit...

Страница 11: ...tion mode optional The device can also be operated with a humidistat The humidistat switches the device on or off depending on the humidity If you choose to operate the device with an optional humidis...

Страница 12: ...positioned correctly Check that the condensation pump functions properly Check for abnormal vibrations and sounds Remove external dirt Check the room temperature Check the device s permissible workin...

Страница 13: ...f necessary X X replace air filter X check for damages X check attachment screws X X carry out a test run X Maintenance and care interval 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 check air inlets and ou...

Страница 14: ...alist companies for cooling and air conditioning or by Trotec Visual check for dirt in the inside of the device 1 Remove the air filter see chapter Cleaning the air inlets and the air filter 2 Shine a...

Страница 15: ...e corners and edges must not be rounded or misshaped Before reinserting the air filter ensure that it is dry and is not damaged Read the chapter Maintenance intervals and replace the air filter punctu...

Страница 16: ...vaporator spacer 11 SD289751 frame right side 40 SD266450 HP switch ACB DB88 400 psi 12 SD291850 crash bar 41 SD266550 LP switch LCB DA15 7 psi 13 SD289850 axle 42 SD188950 rocker switch 1 pole c o 14...

Страница 17: ...8 29 12 29 12 28 1 1 6 1 6 F3A 15 14 16 17 1 3 5 13 14 6 4 2 A1 A2 Note The position numbers of the spare parts differ from those describing the positions of other parts mentioned in this operating ma...

Страница 18: ...e parts differ from those describing the positions of other parts mentioned in this operating manual No Item number Spare part 1 7310001153 console moulding 2 7141000891 pilot light red rectangular 25...

Страница 19: ...ata Dispose of the refrigerant oil mixture appropriately and according to the national regulations in accordance with the EC Low Voltage Directive 2006 95 EC and the EC Directive 2004 108 EC about ele...

Страница 20: ...Trotec GmbH Co KG Grebbener Str 7 D 52525 Heinsberg 49 2452 962 400 49 2452 962 200 info trotec com www trotec com...

Отзывы: