EN
11
dehumidifier TTK 105 S / TTK 105 S HC
•
From the outside, check the condenser for dirt (see
chapter Maintenance). If the condenser is dirty, have it
cleaned by a specialist company or by Trotec.
•
The device might carry out an automatic defrost. During
automatic defrost, the device does not dehumidify.
The device is loud or vibrates:
•
Check whether the device is set up in a stable and upright
position.
Condensate is leaking:
•
Check the device for leaks.
The compressor does not start:
•
Check the room temperature. Observe the device's
permissible operating range according to the technical
data. Possibly, the device does not start because the
ambient temperature is too low (< 5 °C).
•
Ensure that the relative room humidity complies with the
technical data.
•
Check the preselected relative room humidity. The
humidity in the room must be above the selected range.
•
Check whether the overheating protection of the
compressor has tripped. Disconnect the device from the
mains and let it cool down for approx. 10 minutes before
reconnecting it.
•
The device might carry out an automatic defrost. During
automatic defrost, the device does not dehumidify.
The device gets very warm, is loud or loses power:
•
Check the air inlets and air filters for dirt. Remove external
dirt.
•
From the outside, check the device for dirt (see chapter
Maintenance). If the inside of the device is dirty, have it
cleaned by a specialist company for cooling and air-
conditioning or by Trotec.
Your device still does not operate correctly after these
checks?
Please contact the customer service. If necessary, bring the
device to a specialist company for cooling and air-conditioning
or to Trotec for repair.
Error codes
The following error messages can be displayed on the segment
display:
Error code Cause
Remedy
30
Humidity sensor –
circuit interrupted
The humidity level is
lower than 30 % RH.
Switch the device off and
contact the customer
service.
90
Humidity sensor –
short circuit
The humidity level is
higher than 90 % RH.
Switch the device off and
contact the customer
service.
Lo
The current room
temperature is lower
than 0 °C.
Temperature sensor
– circuit interrupted
Activate the dehumidifier at
room temperatures which
comply with the technical
data.
Should the alarm persist,
please contact the
customer service.
Hi
The current room
temperature is higher
than 50 °C.
Temperature sensor
– short circuit
Activate the dehumidifier at
room temperatures which
comply with the technical
data.
Should the alarm persist,
please contact the
customer service.
E5
Chip communication
failure
Switch the device off and
contact the customer
service.