condenser dryer DH 25 S / DH 65 S

Operation

Control panel

Avoid open doors and windows.

After being switched on, the device operates fully
automatically.

The fan runs permanently until the set nominal value is
reached or the device switched off.

After a runtime of approximately 35 minutes the device will
switch over to the defrost mode for a duration of about 
3 minutes, if required.

8

9

10

11 12

13

14

15

16

17

No. Designation

Meaning

8

POWER

 LED

Illuminated during standby and
ongoing operation

9

ALARM

 LED

Illuminated in the event of an error
message

10 Segment display

Indication of the desired room humidity
level

11

WORKING 

LED

Illuminated when the compressor is
switched on

12

FULL

 LED

Illuminated when the condensation
tray is full

13

PUMP

 button

Draining of residual water from the
condensation tray

14

HOUR 

button

Activation or deactivation of the
operating hours display.
The operating hours are indicated on
the segment display (10).

15

Increase value

button

For increasing the desired relative
humidity level (30 % to 80 %)

16

Decrease value

button

For reducing the desired relative
humidity level (30 % to 80 %)

17

POWER

 button

Switching the device on and off

Warning of electrical voltage

Risk of electric shock!
The device does not have the appropriate protection
class for use in wet rooms.
There is a risk of electric shock!
Never use the device in wet rooms (e.g. in bathrooms
and laundry rooms) and never immerse the device in
water!

Switching the device on

Once you have completely installed the device as described in
the chapter Assembly and start-up, you can switch it on.
Press the 

POWER

 button (17). The device starts to dehumidify.

Note

Only use the device in an upright position, otherwise
the compressor could be damaged.

Note

If you switch the device off and back on immediately
afterwards, it will take approx. 4 minutes for the device
to start up again.

Setting the desired room humidity

You can adjust the preset room humidity level at any time
during operation.

1. Press the 

Increase value

 button (15) or 

Decrease

value

 button (16), in order to set the desired value (in

increments of 1 % ranging between 30 % and 80 %).

ð

The segment display flashes while you are making the
setting.

2. The segment display will again be illuminated steadily

approx. 4 s after the last input.

ð

The desired room humidity level is set.

Setting continuous operation

The device dehumidifies the air constantly and regardless of the
relative room humidity.

1. Press the 

Decrease value

 button (16) until the segment

display (10) shows 

Cont

.

Содержание DH 25 S

Страница 1: ...TRT BA DH25S DH65S TC220103TTRT03 004 EN DH 25 S DH 65 S EN ORIGINAL INSTRUCTIONS CONDENSER DRYER...

Страница 2: ...rked with this symbol indicates that the instructions must be observed You can download the current version of the instructions via the following link DH 25 S https hub trotec com id 43847 DH 65 S htt...

Страница 3: ...e refrigerants Only position the device in rooms where potentially leaking refrigerant cannot accumulate Unventilated rooms in which the device is installed operated or stored must be built in a way t...

Страница 4: ...her than the intended use is regarded as a reasonably foreseeable misuse Personnel qualifications People who use this device must be aware of the dangers that occur when working with electric devices...

Страница 5: ...ss for use in wet rooms There is a risk of electric shock Never use the device in wet rooms e g in bathrooms and laundry rooms and never immerse the device in water Warning of electrical voltage Befor...

Страница 6: ...ce operate effectively even at temperatures below 15 C The device has a control panel for operating and controlling the functions Because of the heat radiation generated during operation the room temp...

Страница 7: ...re that the power cable is not damaged and that you do not damage it during unwinding Start up When positioning the device observe the minimum distance from walls or other objects as described in the...

Страница 8: ...drain hose Proceed as follows to connect a condensation drain hose to the device A suitable condensation drain hose 3 4 connection is ready for use The device is switched off 1 Connect the condensatio...

Страница 9: ...e on and off Warning of electrical voltage Risk of electric shock The device does not have the appropriate protection class for use in wet rooms There is a risk of electric shock Never use the device...

Страница 10: ...oned correctly Check the room temperature Observe the device s permissible operating range according to the technical data Ensure that the relative humidity complies with the technical data Check the...

Страница 11: ...the device checked by a specialist company for cooling and air conditioning and have the humidity sensor exchanged if necessary Pro3 The ambient temperature probe is malfunctioning The device will swi...

Страница 12: ...or damage X Check the attachment screws X X Test run X Maintenance and care log Device type Device number Maintenance and care interval 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Check air inlets and outl...

Страница 13: ...a thick layer of dust have the inside of the device cleaned by a specialist company for cooling and air conditioning or by Trotec 5 Put the air filter back in Refrigerant circuit Danger Natural refri...

Страница 14: ...edges of the air filter must not be deformed or rounded Before reinserting the air filter make sure that it is undamaged and dry 1 Remove the air filter 6 at the air inlet from the device 2 Clean the...

Страница 15: ...C 35 to 93 RH 35 to 90 RH 35 to 70 RH 35 to 98 RH 35 to 90 RH 35 to 70 RH Mains connection 220 240V 50 Hz 220 240V 50 Hz Power input 0 7 kW 1 48 kW Nominal current 3 1 A 7 6 A Peak starting current 1...

Страница 16: ...16 EN condenser dryer DH 25 S DH 65 S Wiring diagram DH 25 S...

Страница 17: ...EN 17 condenser dryer DH 25 S DH 65 S Wiring diagram DH 65 S...

Страница 18: ...ing the positions of the components mentioned in these instructions No Spare part No Spare part 1 Shuko plug 9 Evaporator closing Sx 2 Front grille 10 Handle 3 Wheel 50 11 Cover 4 Wheel 50 with brake...

Страница 19: ...ons No Spare part No Spare part 1 Running capacitor 10 Humidity sensor 2 Compressor Kit 11 Side lane humidity sensor 3 Bottom 12 Front lane humidity sensor 4 Sanhua coil 13 Evaporator top 5 Solenoid v...

Страница 20: ...exploded assembly drawing 3 Info The position numbers of the spare parts differ from those describing the positions of the components mentioned in these instructions No Spare part No Spare part 1 card...

Страница 21: ...describing the positions of the components mentioned in these instructions No Spare part No Spare part 1 Display label 8 Filter lane 2 Display support 9 Rear grille 3 Display 10 Filter filter holder 4...

Страница 22: ...tioned in these instructions No Spare part No Spare part 1 Running capacitor 9 Humidity sensor 2 Compressor Kit 10 Evaporator top 3 Bottom 11 Lower condensate tray 4 Sanhua coil 12 Thermostat K50 5 So...

Страница 23: ...assembly drawing 3 Info The position numbers of the spare parts differ from those describing the positions of the components mentioned in these instructions No Spare part No Spare part 1 cardboard box...

Страница 24: ...on the nameplate Dispose of the refrigerant appropriately and according to the national regulations Only for United Kingdom According to Waste Electrical and Electronic Equipment Regulations 2013 2013...

Страница 25: ...Trotec GmbH Grebbener Str 7 D 52525 Heinsberg 49 2452 962 400 49 2452 962 200 info trotec com www trotec com...

Отзывы: