background image

T70Z electric shower

8

Table B

Note: 

Cable selection is dependent on 

derating factors

Twin and earth PVC insulated cable

Current carrying capacity

In conduit

trunking

6mm²

38A

10mm²

52A

16mm²

69A

Installed in an 

insulated wall

6mm²

32A

10mm²

43A

16mm²

57A

Clipped direct

or buried in a 
non-insulated 

wall

6mm²

46A

10mm²

63A

16mm²

85A

6mm2

10mm2

16mm2

*The method below may be used by

installers to determine the approximate 

size of the incoming cable.

1.

Measure the width of an individual strand,
and half that measurment to find 

(r)

,

e.g: 

1.34mm ÷ 2 = (r) 0.67mm

2.

Multiply 

(r) x (r)

 x 

3.14,

e.g: 

(r)

 

0.67 x (r)

 

0.67 

3.14 = 1.41mm2

3.

Multiply this by the number of wire strands
(usually 7), e.g: 

1.41mm2 x 7 = 9.87mm2.

4.

The number obtained would suggest

10mm2

 wiring.

*PLEASE NOTE:

 If unsure, consult a qualified Electrician.

6

 

A 45 amp double pole isolating switch with 
a minimum contact gap of 3mm in both 
poles must be incorporated in the circuit.

6.1

  It must have a mechanical indicator showing 

when the switch is in the OFF position, and 
the wiring must be connected to the switch 
without the use of a plug or socket outlet.

6.2

 The switch must be accessible and clearly 

able, but out of reach of a person 

u

xed bath or shower, except for the

cord of a cord operated switch, and should
be placed so that it is not possible to touch
the switch body while standing in a bath or
shower cubicle. It should be readily accessible
to switch off after using the shower.

7

 

Where shower cubicles are located in any 
rooms other than bathrooms, all socket 
outlets in those rooms must be protected by 
a 30mA RCD.

8

 

The current carrying capacity of the cable 
must be at least that of the shower circuit 
protection 

(see Table B)

.

8.1

  To obtain full advantage of the power 

provided by the shower, use the shortest 
cable route possible from the consumer unit 
to the shower.

8.2

  It is also necessary to satisfy the disconnection 

time and thermal constraints which means 
that for any given combination of current 
demand, voltage drop and cable size, there is 
a maximum permissible circuit length.

9

 

The shower circuit should be separated from 
other circuits by at least twice the diameter 
of the cable or conduit.

9.1

  The current rating will be reduced if the 

cabling is bunched with others, surrounded 
by thermal loft or wall insulation or placed 
in areas where the ambient temperature 
is above 30°C. Under these conditions, 
derating factors apply and it is necessary to 
select a larger cable size.

9.2

  In the majority of installations 

(see 

Table B)

, the cable will unavoidably be 

placed in one or more of the above 
conditions. This being so, it is strongly 
recommended to use a minimum of 10mm 
cabling throughout the shower installation.

9.3

  In any event, it is essential that individual 

site conditions are assessed by a competent 
electrician in order to determine the correct 
cable size and permissible circuit length.

Содержание T70Z

Страница 1: ...hen not in use This is a safety procedure recommended for all electrical appliances The shower head and hose supplied with this product are a safety critical part of your shower Failure to use genuine...

Страница 2: ...s appliance is intended to be permanently connected to the water mains and not connected by a hose set A suitable double pole isolation switch for supply disconnections must be incorporated in the fix...

Страница 3: ...ust comply with Water Regulations Building Regulations or any particular regulations as specified by Local Water Company or Water Undertakers and should be in accordance with BS EN 806 2 2 The supply...

Страница 4: ...ler than in the summer so the flow rate will vary between seasons at any one temperature setting At different times of the year you may have to adjust the position of the temperature control to mainta...

Страница 5: ...quirements 9 Siting of the shower 10 PRD Pressure Relief Device 10 Fitting the shower to the wall 11 13 Pipe access points front cover 12 Plumbing connections 14 Electrical connections 15 Replacing th...

Страница 6: ...100mm 300mm ENTRY POINTS DIMENSIONS WATER Left Bottom Back Top Right Bottom Back CABLE Left Bottom Back Top Right Bottom Back Top Z uni fit kit required Back Back Others Others Inlet connection 15mm d...

Страница 7: ...he whole installation at the mains supply and remove the correct fuse 3 The shower must be connected to its own independent electrical circuit IT MUST NOT be connected to a ring main spur socket outle...

Страница 8: ...g in a bath or shower cubicle It should be readily accessible to switch off after using the shower 7 Where shower cubicles are located in any rooms other than bathrooms all socket outlets in those roo...

Страница 9: ...hower for full performance for 7 5Kw 8 5Kw Maximum static pressure 1000 kPa 10 bar Maximum inlet temperature 28 C Minimum inlet temperature 2 C Fig 5 shows a typical system layout Do not use jointing...

Страница 10: ...ead be constrained by a fixed or sliding attachment so that it can only discharge water at a point not less than 25mm above the spill over level of the relevant bath shower tray or other fixed applian...

Страница 11: ...ntegral part of the cover DO NOT attempt to remove them Lift the cover from the backplate Entry points can be found on page 6 The water inlet fig 7 has been designed to allow left or right fitting To...

Страница 12: ...op entry has been chosen remove the appropriate pipe cover If bottom entry has been chosen carefully remove the appropriate cut out using a junior hacksaw Please note The bottom cut outs are not desig...

Страница 13: ...e location of the fixing holes in the backplate are shown in fig 10 Drill and plug the wall An appropriate drill bit should be used If the wall is brick plasterboard or a soft building block appropria...

Страница 14: ...r IMPORTANT Before completing the connection of the water supply to the inlet of the shower flush out the pipework to remove all swarf and system debris This can be achieved by connecting a hose to th...

Страница 15: ...cable must be stripped back to the minimum The supply cable must be secured either by routing through conduit or in trunking or by embedding in the wall in accordance with current IEE regulations The...

Страница 16: ...wise until the flat section is at the bottom fig 13 2 With the cover off the shower turn the stabiliser valve spindle fully clockwise until resistance is felt fig 14 4 With the cover off the shower tu...

Страница 17: ...control to MINIMUM FLOW may cause the PRD to operate 2 Turn on the electric and mains water supplies to the shower 3 Turn the power selector to the COLD setting fig 18 and wait until water starts to...

Страница 18: ...he shower head it will not alter the water temperature The RED symbol is an economy setting for using less energy when the ambient mains water temperature is high during warmer months Temperature adju...

Страница 19: ...advisable to be certain that the showering temperature is satisfactory by testing with your hand before stepping under the shower head There will always be a time delay of a few seconds between select...

Страница 20: ...the device will disconnect the heating elements It will require a visit from a qualified engineer to determine the nature of the fault and replace the safety device once the unit has been repaired Tw...

Страница 21: ...lectricity supply and water supply at the mains The inlet filter is situated in the bottom of the inlet pipe fig 20 To gain access to the filter remove the cover and then unscrew the assembly from the...

Страница 22: ...flow rate via temperature control Is water supply mains or tank fed If tank fed replumb to mains water supply or see 4 2 4 If mains fed make sure that the mains stopvalve is fully open and there are n...

Страница 23: ...4 3 1 4 3 2 4 4 1 5 1 1 6 1 1 6 2 1 6 3 1 6 4 1 7 1 1 7 2 1 7 3 1 required see rating label Reduction in ambient water temperature Electrical malfunction or safety cut out operated Water pressure has...

Страница 24: ...e DTS registration number DTS 501317 1 All our electric products are labelled accordingly with the crossed out wheeled bin symbol This indicates for disposal purposes at end of life that these product...

Страница 25: ...2 HEATER ELEMENTS USED HEATER ELEMENTS USED NONE OF THE ELEMENTS USED 0 1 2 1 OF THE ELEMENTS USED HEATER ELEMENTS USED 2 OF THE ELEMENTS USED 0 1 2 H O T HOT COLD Power Knob settings Temperature Kno...

Страница 26: ...T70Z electric shower 26...

Страница 27: ...T70Z electric shower 27...

Страница 28: ...xpress or Diners Card Payment can also be made by pre payment of a pro forma invoice by cheque or postal order Telephone orders are based on information given during the call Before contacting Triton...

Отзывы: